1 using the auto/off/manual switch (figure 4.1), 2 automatic transfer operation, 3 sequence of automatic operation – Generac Power Systems 05176-0 User Manual

Page 16: 1 “auto” position, 2 “off” position, 3 “manual” position, Figure 4.1 – generator control panel

Advertising
background image

14

Section 4 — Operation

Air-cooled 15 kW Generators

4.1

USING THE AUTO/OFF/MANUAL
SWITCH (FIGURE 4.1)

4.1.1 “AUTO”

POSITION

Selecting this switch position activates fully automatic
system operation. It also permits starting and exercising
of the engine every seven days with the exercise timer
(see "Generator Test Under Load"). This position also is
used for remote starting, when it is set up.

4.1.2 “OFF”

POSITION

This switch position shuts down the engine. This
position also prevents automatic operation.

4.1.3 “MANUAL”

POSITION

Set the switch to MANUAL to crank and start the
engine. Transfer to standby power will not occur
unless there is a utility failure.

Figure 4.1 – Generator Control Panel

HIGH TEMP.

OVER SPEED

LOW OIL

SYSTEM SET

OVER CRANK

MAN.

SET

OFF

AUTO

15A

FUSE

EXERCISE

TIME

R

POWER SYSTEMS, INC.

L o c a t e y o u r

n e a r e s t

d e a le r

a t :

R

FUSE

5A

E X E R C IS E R

N O T

S E T

N O

U T IL IT Y

S E N S E

4

F L A S H IN G R E D

L E D S =

F L A S H IN G G R E E N

L E D =

With the switch set to AUTO, the engine may

crank and start at any time without warning.
Such automatic starting normally occurs when
utility power source voltage drops below a pre-
set level or during the normal exercise cycle. To
prevent possible injury that might be caused by
such sudden starts, always set the switch to OFF
and remove both fuses before working on or
around the generator or transfer switch. Then,
place a “Do Not Operate” tag on the generator
panel and on the transfer switch.

4.2

AUTOMATIC TRANSFER
OPERATION

To select automatic operation, do the following:

1. Make sure the transfer switch main contacts are

set to their “Utility” position, i.e., loads connected
to the utility power source (Figure 4.2).

2. Be sure that normal utility power source voltage

is available to transfer switch terminal lugs N1

‹

‹

‹

and N2.

3. Set the generator’s AUTO/OFF/MANUAL switch to

AUTO.

4. Set the generator’s main circuit breaker to its ON

(or closed) position.

With the preceding steps complete, the generator will
start automatically when utility source voltage drops
below a preset level. After the unit starts, loads are
transferred to the standby power source. Refer to
“Sequence of Automatic Operation.”

4.3

SEQUENCE OF AUTOMATIC
OPERATION

The generator’s control panel houses a control logic
circuit board. This board constantly monitors util-
ity power source voltage. Should that voltage drop
below a preset level, circuit board action will signal
the engine to crank and start. After the engine starts,
the circuit board signals the transfer switch to acti-
vate and connect load circuits to the standby power
supply (load terminal lugs T1/T2 connect to terminal
lugs E1/E2).
Upon restoration of utility source voltage above a
preset level, generator circuit board action signals the
transfer switch to transfer loads back to that power
supply. After retransfer, the engine is signalled to shut
down.
The actual sequence of operation is controlled by
sensors and timers on a control logic circuit board,
as follows:

A. Utility Voltage Dropout Sensor

• This sensor monitors utility source voltage.
• If utility source voltage drops below about 70

percent of the nominal supply voltage, the sensor
energizes a 15-second timer.

• Once the timer has expired, the engine will crank

and start.

B. Engine Warm-up Time Delay

• This mechanism lets the engine warm up for

about 10 seconds before the load is transferred
to a standby source.

C. Standby Voltage Sensor

• This sensor monitors generator AC output volt-

age. When the voltage has reached 50 percent of
the nominal rated voltage, transfer to standby
can occur.

D. Utility Voltage Pickup Sensor

• This sensor monitors utility power supply volt-

age. When that voltage is restored to above 70
percent of the nominal source voltage, a retrans-
fer time delay starts timing.

E. Retransfer Time Delay

• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action

de-energizes the transfer relay in the transfer
switch.

Advertising