25

Maintenance Level 1

Level 2

Level 3

Level 4

Level5

Tasks

Recom-

Task

Task Required Task

Task Required Task

mended

Comp.

Comp. to be done Comp.

Required

Comp. to be done Comp.

to be done (Date- Required (Date-

Semi-

(Date- to be done (Date-

Bi-

(Date-

monthly/

Initials) to be done Initials) annually/

Initials)

Annually/ Initials) annually/ Initials)

10 hrs.

6 months

50 hrs.

100 hrs.

250 hrs.

10. Test the engine

and transfer

switch safety

devices. Correct

and/or adjust as

necessary.

11. Initiate an

automatic start

and transfer of

the unit to site

load and exercise

it for at least 1

hour looking for

leaks, loose

connections or

components, and

abnormal

operating

conditions.

Correct as

necessary.

12. Start and

exercise the unit

at full rated load

(use a load bank

if the site load is

not enough) for

at least 2 hours

looking for leaks,

loose

connections or

components, and

abnormal

operating

conditions.

Correct as

necessary.

13. Perform an

engine oil

analysis (send a

sample to a lab

for results).

Change the

engine oil and

filters if the

analysis results

indicate this is

required.

14. Change the

*

engine oil.

15. Replace the

*

engine oil filter(s).

Section 5 — Maintenance

Air-cooled 15 kW Generators

* Change oil and fi lter after fi rst eight (8) hours of operation and then every 100 hours thereafter. Change sooner when operating under a heavy load or in

a dusty or dirty environment or in high ambient temperatures.