21

When valve clearance is correct, hold the pivot ball
stud in place with the allen wrench and tighten the
rocker arm jam nut. Tighten the jam nut to 174
in/lbs. torque. After tightening the jam nut, recheck
valve clearance to make sure it did not change.

Figure 5.6 - Valve Clearance Adjustment

Jam Nut

Pivot Ball

Stud

Rocker

Arm

Valve

Stem

• Install new valve cover gasket.
• Re-attach the valve cover.

NOTE:

Start all four screws before tightening or it will not
be possible to get all the screws in place. Make
sure the valve cover gasket is in place.

• Re-attach the spark plug wire to the spark plug.
• Repeat the process for the other cylinder.

5.9 COOLING

SYSTEM

Air inlet and outlet openings in the generator com-
partment must be open and unobstructed for con-
tinued proper operation. This includes such obstruc-
tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the
engine/generator quickly overheats, which causes it
to quickly shut down. (See Figure 5.7 for vent loca-
tions.)

The exhaust from this product gets extremely

hot and remains hot after shutdown. High grass,
weeds, brush, leaves, etc. must remain clear of
the exhaust. Such materials may ignite and burn
from the heat of the exhaust system.

The maximum ambient temperature for the

generator is 48.9° C (104° F).

Figure 5.7 – Cooling Vent Locations

5.10 ATTENTION AFTER SUBMERSION

If the generator has been submerged in water,
it MUST NOT be started and operated. Following
any submersion in water, have an Authorized Dealer
thoroughly clean and dry the generator.

5.11 CORROSION PROTECTION

Periodically wash and wax the enclosure using auto-
motive type products. Frequent washing is recom-
mended in salt water/coastal areas. Spray engine
linkages with a light oil such as WD-40

®

.

5.12 OUT OF SERVICE PROCEDURE

5.12.1 REMOVAL FROM SERVICE

If the generator cannot be exercised every seven days,
and it is to be out of service longer than 90 days, pre-
pare the generator for storage as follows:

1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line

and allow the unit to shut down.

3. Once the unit has shut down, it will signal a low

oil fault.

4. Set the AUTO/OFF/MANUAL switch to OFF and

turn off the utility power to the transfer switch.

5. While the engine is still warm from running,

drain the oil completely. Refill the crankcase with
oil. See ”Engine Oil Recommendations”.

6. Attach a tag to the engine indicating the viscosity

and classification of the oil in the crankcase.

7. Remove the spark plugs and spray fogging agent

into the spark plugs threaded openings. Reinstall
and tighten the spark plugs.

8. Remove the battery and store it in a cool, dry

room on a wooden board. Never store the battery
on any concrete or earthen floor.

9. Clean and wipe the entire generator.

‹

Section 5 — Maintenance

Air-cooled 15 kW Generators