GE GEH-5304A User Manual

Page 11

Advertising
background image

GEH-5304A

11

Mounting may be either horizontal or vertical for these bearing life determinations, as long as no axial
load (i.e., suspended load) other than the weight of the armature is present if vertical.

5.

Special Load Considerations

Where the load is overhung beyond the motor shaft extension or greater bearing life is desired, the
application should be referred to GE Industrial Systems.

6.

Pinion Drives

While Kinamatic

motors are not designed for overhung pinion drives, they may be successfully ap-

plied under suitable conditions. In addition to a radial load, some gears produce thrust load on the
bearing. Complete details of the proposed gearing should be referred to GE Industrial Systems in all
cases.

7.

Thrust Loads

Due to the mounting position or type of drive arrangement, a thrust load may be applied to the motor
shaft. The Kinamatic

motor is designed to permit a limited amount of thrust load. This permissible

load will vary by mounting position and direction of the load due to the weight of the armature. The
permissible load in Table 2 is tabulated by frame diameter and mounting position. These apply to
ball bearings only.

For applications combining thrust and radial loads or where thrust loads exceed the values shown in
Table 2, refer all details to GE Industrial Systems.

Table 2

Maximum Continuous Thrust Capacity, Lbs.*

Vertical Mounting

Bearing

Horizontal

Thrust Load

Thrust Load

Frame

Size

Mounting

Up

Down

2512

Std-309

350

465

235

2512

O/S-310

400

515

285

2513

Std-309

350

485

215

2513

O/S-310

400

585

265

2812

Std-310

400

550

250

2812

O/S-311

500

650

350

2813

Std-310

400

585

215

2813

O/S-311

500

685

315

*Based on L10 life of 20,000 hours and an average speed not exceeding 2500 RPM.

IV.

OPERATION

Disconnect power before touching any internal part. High voltage may be pres-
ent even when the machine is not rotating. If used with a rectified power sup-
ply, disconnect all AC line connections to power supply. With other power
supplies, disconnect all DC line and field connections. Also disconnect power
from auxiliary devices.

Ground the machine properly to avoid serious injury to personnel. Grounding
must be in accordance with the National Electrical Code and consistent with
sound local practices. One of the bolts holding the conduit box to the unit, ac-
cessible from inside the conduit box, is identified and may be used for attach-
ing a grounding cable.