Thermostats automatically reset after the motor has cooled somewhat. In order
to prevent property damage or injury to personnel, the control circuit should be
designed to prevent re-energizing of the motor when the thermostat resets.

Table 5

Maximum Current Ratings for Thermostats

on Dripproof and Totally Enclosed Motors

(Normally open or normally closed contacts)

Load

125 VAC

250 VAC

600 VAC

30 VDC

Do not use above 600 VAC or 30 VDC

Resistive

5

Amps

2.5 Amps

1

Amp

5

Amps

Inductive*

3

Amps

1.5 Amps

0.5 Amps

1.5 Amps

*Suitable for pilot duty only (relay coils).

H.

Speed Limit Device

The mechanical speed limit device is non-adjustable. Tripping speed is specified by a note on the print cer-
tification for each specific order.

The speed limit electrical contacts are normally closed and are usually connected in relay or holding circuits.
Current ratings are the same as those listed in Table 5.

A speed limit device is furnished on machines only when ordered.

The contacts of the speed limit device automatically reclose after the speed has
fallen below the trip value. In order to prevent property damage or injury to
personnel, the control circuit should be designed to prevent re-energizing the
motor until the cause of the overspeed has been corrected.

Table 6

Lead Markers

Function

Winding

Armature

A1, A2

Field (Shunt)

F1, F2, F3, F4, etc.

Stator, AC Machines Only

T1, T2, T3, T4, etc.

(Type AN Tachometer Generator)

Accessories & Special Device Markings

Tachometer Generator, Direct Current, to Terminal Board

A1, A2

Brake Coil Leads

B1, B2, B3, B4, etc.

Heater, Brake Space Heater

BH1, BH2, BH3, BH4, etc.

Brake Interlock Switch

BS1, BS2, BS3, BS4, etc.

Heater, Space Heater in the Machine

H1, H2, H3, H4, etc.

Thermostat

P1, P2, P3, P4, etc.

Resistance Temperature Detector (RTD)

R1, R2, R3, R4, etc.

I.

Space Heater

When furnished, see Print Certification for Electrical Rating.

Space heaters are furnished in machines when ordered. They should be energized with the correct AC volt-
age as shown on the nameplate.