Greenheck Fan IMO-XXX User Manual

Page 3

Advertising
background image

connection and Operation of temperature

Response devices (RRl standard, OcI option,

and PRv option)

RRl - Dampers will be supplied with a thermostat-type
temperature response device, as a standard. The device is a RRL
(resettable link device), which only incorporates one thermostat
and therefore the damper remains closed as soon as its sensor
temperature is reached. The RRL does not contain blade
indication switches. Refer to figure 5 for wiring of the RRL
thermostat.
If RRL is ordered with a pneumatic actuator, an EP switch is
required with an appropriate electric power circuit to allow the
electric thermostat to control the pneumatic actuator.

OcI - The OCI (open or closed indicator) option contains a single
pole, double throw switch used to indicate the damper blade
position. The switch provides a positive open or closed signal
when used in conjunction with remote indicator lights. Refer to
fig. 7 for wiring of the OCI option.

PRv - The PRV (pneumatic relief valve) option is heat responsive
device used with pneumatic actuators. This can be used in place
of EP switch where a RRL is used. The PRV activates when
temperature in excess of the temperature of the fusible link are
detected. When the fusible link melts, air from the actuator is
exhausted to close the dampers. Pneumatic actuators are to be
piped per local code.

RatINGS

Integral Switch type: Single Pole, double throw

electrical capacity: 10 Amps,

1

/

3

hp, 120 or 240 Vac

1

/

2

Amp, 125 Vdc;

1

/

4

Amp 250 Vdc

5 Amps, 120 Vac “L” (lamp load)
1.0 Amps, 24 Vac
1.5 Amps, 24 Vdc

temperature limit: 165° F (standard primary sensor)

212° F (optional primary sensor)

L1

DAMPER

INDICATOR

LIGHTS

L2

CLOSED POSITION OF THE DAMPER.

A BLUE MARKER INDICATE THE

THE SWITCH WIRES WRAPPED WITH

NOTE:

YELLOW

ELECTRICAL CAPACITY = 10AMP @ 120 / 240 VAC

YELLOW

YELLOW

YELLOW

NO

NO

S2

S1

BY OTHERS

OcI Wiring

Fig. 5

Fig. 6

L1

M

L2

ELECTRIC DAMPER

ACTUATOR OR PNEUMATIC

SOLENOID VALVE

PRIMARY TEMP

SENSOR

ELECTRICAL CAPACITY = 10 AMP @ 120 / 240 VAC

BLACK

ORANGE

P

NC

BLACK

WHITE/RED

RRl Wiring

Damper model

Maximum Single

Maximum Overall size for

Section size

Multi-section dampers

IMO-310

32 in. x 32 in.

64 in. x 32 in.

(813mm x 813mm)

(1626mm x 813mm)

SSIMO-310

32 in. x 32 in.

64 in. x 32 in.

(813mm x 813mm)

(1626mm x 813mm)

IMO-311

32 in. x 32 in.

64 in. x 32 in.

(813mm x 813mm)

(1626mm x 813mm)

SSIMO-311

32 in. x 32 in.

64 in. x 32 in.

(813mm x 813mm)

(1626mm x 813mm)

Size limitations

Manually operated dampers (IMO-310 & SSIMO-310)

Manually operated dampers utilize a spring and fusible link assembly to close the damper during elevated temperature
conditions. No electrical power is required for these models.

Motor operated dampers (IMO-311 & SSIMO-311)

Motor operated dampers are supplied with an electric thermal response device which cuts power to the spring return
actuator upon sensing an elevated temperatures. See below for electrical connections.