Filter options, Model selection procedure, Model sq model bsq – Greenheck Fan SQ User Manual

Page 8

Advertising
background image

8

Filter Options

The filter box is designed to provide a compact and convenient clean air solution.
Factory assembled as a single unit, this fan eliminates the costly process of
designing, fabricating, and installing special remote filter box assemblies. Both
the fan and filter section feature removable access panels on both sides to
remove and replace filters, making fan maintenance simple and fast.

Model

A

B

C

D

WT. Filter Size

Filter

Quantity

SQ-60 - 75

22

1

8

(562)

12

(305)

8

7

8

(225)

1

(25)

40

(18)

10 x 12

(254 x 305)

1

SQ-80 - 95

45

5

8

(1159)

15

(381)

11

7

8

(302)

1

(25)

74

(34)

14 x 25

(356 x 635)

1

SQ-100

47

1

4

(1200)

17

(432)

13

7

8

(352)

1

(25)

88

(40)

16 x 20

(406 x 508)

2

SQ-120

52

3

16

(1326)

19

(483)

15

7

8

(403)

1

(25)

114

(52)

16 x 25

(406 x 635)

2

SQ-130

46

3

8

(1178)

21

(533)

17

7

8

(454)

1

(25)

120

(54)

20 x 20

(508 x 508)

2

SQ-140

52

3

8

(1330)

23

(584)

19

7

8

(505)

1

(25)

174

(79)

20 x 25

(508 x 635)

2

SQ-160

51

3

8

(1305)

26

(660)

22

7

8

(581)

1

(25)

246

(112)

20 x 20

(508 x 508)

4

BSQ-70 - 80 - 90 50

5

8

(1286)

15

(381)

11

7

8

(302)

1

(25)

117

(53)

14 x 25

(356 x 635)

1

BSQ-100

47

1

4

(1200)

17

(432)

13

7

8

(352)

1

(25)

120

(54)

16 x 20

(406 x 508)

2

BSQ-120

52

3

16

(1326)

19

(483)

15

7

8

(403)

1

(25)

144

(79)

16 x 25

(406 x 635)

2

BSQ-130 - 130HP 46

3

8

(1178)

21

(533)

17

7

8

(454)

1

(25)

140

(64)

20 x 20

(508 x 508)

2

BSQ-140 - 140HP 52

3

8

(1330)

23

(584)

19

7

8

(505)

1

(25)

181

(82)

20 x 25

(508 x 635)

2

BSQ-160 - 160HP 51

3

8

(1305)

26

(660)

22

7

8

(581)

1

(25)

294

(133)

20 x 20

(508 x 508)

4

BSQ-180 - 180HP 55

1

16

(1399)

28

(711)

23

7

8

(606)

1

1

2

(38)

344

(156)

20 x 25

(508 x 635)

4

BSQ-200 - 200HP 66

11

16

(1694)

32

(813)

27

7

8

(708)

1

1

2

(38)

441

(200)

12 x 25

(305 x 635)

3

16 x 25

(406 x 635)

3

BSQ-240 - 240HP 68

7

8

(1749)

39

(991)

34

7

8

(886)

1

1

2

(38)

573

(260)

20 x 25

(508 x 635)

4

16 x 25

(406 x 635)

4

BSQ-300 - 300HP 72

1

8

(1832)

46

(1168)

41

7

8

(1064)

1

1

2

(38)

759

(344)

20 x 25

(508 x 635)

8

BSQ-360 - 360HP 79

1

4

(2013)

52

(1321)

47

7

8

(1216)

1

1

2

(38)

957

(434)

16 x 25

(406 x 635)

10

20 x 25

(508 x 635)

5

BSQ-420

93

1

8

(2365)

58

(1473)

53

7

8

(1368)

1

1

2

(38)

1185

(538)

16 x 25

(406 x 635)

5

20 x 25

(508 x 635)

10

Note: 24-inch side clearance is recommended for accessing and removing filters.

All dimensions in inches (millimeters) and weight (WT.) in pounds (kilograms).

Model Selection Procedure

1. Calculate system pressure drop and CFM

requirements (not including filters).

2. Make a preliminary model size selection.
3. Calculate a filter pressure drop for the

preliminary model size selected in step 2 using
the equation:

P = Fx (

10,000

)

2

4. Add the filter pressure drop (P) to the system

pressure drop and make a revised model
size selection. Use the charts on the left to
determine filter factor (F).

cfm

Model Size

1 in.

Aluminum

Filter

Factor (F)

1 in.

Paper

Filters

2 in.

Aluminum

Filters

2 in.

Paper

Filters

SQ

BSQ

60-65-70-75

186

318.06

251.1

303.18

80-85-90-95 70-80-90

21.8

37.278

29.43

35.534

100

100

8.72

14.9112 11.772 14.2136

120

120

5.58

9.5418

7.533

9.0954

130

130

5.58

9.5418

7.533

9.0954

140

140

3.57

6.1047

4.8195

5.8191

160

160

2.09

3.5739

2.8215

3.4067

180

1.34

2.2914

1.809

2.1842

200

0.77

1.3167

1.0395

1.2551

240

0.41

0.7011

0.5535

0.6683

300

0.33

0.5643

0.4455

0.5379

360

0.15

0.2565

0.2025

0.2445

420

0.13

0.2223

0.1755

0.2119

Model SQ

Model BSQ

B

A

B

C

C

A

C

D

C

D

Optional cover varies

with motor size.

Recommend 24 in.

clearance.

D

D

B

A

B

C

C

A

C

D

C

D

Optional cover varies

with motor size.

Recommend 24 in.

clearance.

D

D

Advertising