Testing rotor insulation, The megohmmeter – Generac Power Systems Quietpact 75 User Manual

Page 16

Advertising
background image

S

Se

ec

cttiio

on

n 3

3

IIN

NS

SU

UL

LA

AT

TIIO

ON

N R

RE

ES

SIIS

ST

TA

AN

NC

CE

E T

TE

ES

ST

TS

S

TEST BETWEEN PARALLEL WINDINGS:
Connect the tester leads across Stator leads No. 11P
and 33. Apply a voltage of 1500 volts. If an insulation
breakdown is indicated, clean and dry the Stator.
Then, repeat the test between parallel windings. If the
Stator fails the second test, replace it.

Figure 3-2. – Stator Leads

TESTING ROTOR INSULATION

To test the Rotor for insulation breakdown, proceed
as follows:

1. Disconnect wires from the Rotor brushes or remove the brush

holders with brushes.

2. Connect the tester positive (+) test lead to the positive (+) slip

ring (nearest the Rotor bearing). Connect the tester negative (-)
test lead to a clean frame ground (like the Rotor shaft).

Figure 3-3. – Rotor Test Points

3. Apply 1000 volts. DO NOT APPLY VOLTAGE LONGER THAN

1 SECOND.

If an insulation breakdown is indicated, clean and dry
the Rotor then repeat the test. Replace the Rotor if it
fails the second test (after cleaning and drying).

THE MEGOHMMETER

GENERAL:
A megohmmeter, often called a “megger”, consists of
a meter calibrated in megohms and a power supply.
Use a power supply of 1500 volts when testing
Stators; or 1000 volts when testing the Rotor. DO
NOT APPLY VOLTAGE LONGER THAN ONE (1)
SECOND.

TESTING STATOR INSULATION:
All parts that might be damaged by the high megger
voltages must be disconnected before testing. Isolate
all Stator leads (Figure 3-2) and connect all of the
Stator leads together. FOLLOW THE MEGGER
MANUFACTURER'S INSTRUCTIONS CAREFULLY.
Use a megger power setting of 1500 volts. Connect
one megger test lead to the junction of all Stator
leads, the other test lead to frame ground on the
Stator can. Read the number of megohms on the
meter.

MINIMUM INSULATION

GENERATOR RATED VOLTS

RESISTANCE

=

__________________________

+1

(in “Megohms”)

1000

The MINIMUM acceptable megger reading for Stators
may be calculated using the following formula:
EXAMPLE: Generator is rated at 120 volts AC.
Divide “120” by “1000” to obtain “0.12”. Then add
“1” to obtain “1.12” megohms. Minimum
Insulation resistance for a 120 VAC Stator Is 1.12
megohms.
If the Stator insulation resistance is less than the cal-
culated minimum resistance, clean and dry the Stator.
Then, repeat the test. If resistance is still low, replace
the Stator.
Use the Megger to test for shorts between isolated
windings as outlined “Stator Insulation Resistance”.
Also test between parallel windings. See “Test
Between Parallel Windings”on this page.

TESTING ROTOR INSULATION:
Apply a voltage of 1000 volts across the Rotor posi-
tive (+) slip ring (nearest the rotor bearing), and a
clean frame ground (i.e. the Rotor Shaft). DO NOT
EXCEED 1000 VOLTS AND DO NOT APPLY VOLT-
AGE LONGER THAN 1 SECOND. FOLLOW THE
MEGGER MANUFACTURER'S INSTRUCTIONS
CAREFULLY.

R

RO

OT

TO

OR

R M

MIIN

NIIM

MU

UM

M IIN

NS

SU

UL

LA

AT

TIIO

ON

N R

RE

ES

SIIS

ST

TA

AN

NC

CE

E::

1

1..5

5 m

me

eg

go

oh

hm

ms

s

Page 14

Advertising
This manual is related to the following products: