Selection guidelines, Motor specifications, Mca example calculation – Greenheck Fan Energy Recovery Ventilator ERV User Manual

Page 14

Advertising
background image

14

Selection Guidelines

Motor Specifications

Blower motor information
must be specified to select
unit. The horsepower,
voltage, phase and enclosure
availability is presented
in the table on the right. If
exhaust and supply blower
horsepower are different,
consult the CAPS program.

Minimum Circuit Amps (MCA) Calculations for ERV Units

Wheel drive, 24 volt internal control amp and standard electric preheat kW. Single or three phase ERV units

Model

Wheel Drive Amps

24v

Control

Amps

Standard Electric Preheat kW

115 208/230 460

115/1 208/1 230/1

208/3

230/3

460/3

ERV-251

0.6

0.6

NA

0.5

2.5

2.1, 4.1 2.5, 5

NA

NA

NA

ERV-361

NA

1.2

0.6

1

NA

NA

NA

4.1, 8.2, 12.3

5, 10, 15

5, 10, 15

ERV-521

NA

2.8

1.4

1

NA

NA

NA

8.2, 12.3,

15.5

10, 15, 19 10, 15, 20, 25, 30

ERV-581

NA

1.6

0.8

1

NA

NA

NA

12.3, 15.5

15, 19

15, 20, 25, 30, 38

ERV-522

NA

5.6

2.8

1

NA

NA

NA

15.5

19

20, 25, 30, 45

ERV-582

NA

3.2

1.6

1

NA

NA

NA

15.5, 24.5

19, 30

20, 38, 50

NA = not available

Model

Open

TE

Two Speed Open

115/1 230/1 230/460/3 230/1 230/460/3 230/1 230/460/3

ERV-251S*

1

4

1

4

-

-

-

-

-

ERV-251H*

1

2

1

2

-

-

-

-

-

ERV-361*

-

1

4

- 2

1

4

- 2

1

4

- 2

1

4

- 2

1

2

- 1

1

2

- 1

1

2

ERV-521*

-

1

2

- 3

1

2

- 5

1

2

- 1

1

2

1

2

- 5

1

2

- 1

1

2

- 3

ERV-581*

-

-

1 - 5

-

1 - 5

-

1 - 3

ERV-522*

-

1

1

2

- 3 1

1

2

- 15

1

1

2

1 - 15

-

1 - 7

1

2

ERV-582*

-

-

1

1

2

- 15

-

1 - 15

-

1 - 7

1

2

UL Listing is available on most open drip proof motors.
*Energy wheel drive motor is only available with open drip proof motors

.

MCA Example Calculation

Greenheck ERV selected: ERV-361S-B, 2 hp
supply motor, 1

1

2

hp exhaust motor, 15kW

preheater operating at 460 volt, three phase.
Step 1: Consult NEC table (not shown) for 2 hp

supply motor amps = 3.4 A

Step 2: Consult NEC table (not shown) for 1

1

2

hp

exhaust motor amps = 2.6 A

Step 3: Calculate 15kW preheater amp draw =

15,000W/

[

460 * 3

]

= 18.8 A

If no preheater is used skip step 3

Step 4: Wheel drive amps for ERV-361 from

table above = 0.6 A

Step 5: 24v Control Amps for ERV-361 from

table above = 1.0 A

Step 6: MCA = Amperage total from steps

1 thru 5 x 1.25

MCA = (3.4 + 2.6 + 18.8 + 0.6 + 1.0)
1.25 = 33 A

Note: Calculations are approximate, use our Computer Aided Product Selection (CAPS) program for exact
MCA calculations.

Filter Pressure Drop

Model

CFM

Intake Hood

with 2-inch

aluminum

filters

Pleated

2-inch

filters

ERV-251

500

0.09

0.09

1,000

0.32

0.19

ERV-361

1,000

0.09

0.10

2,200

0.45

0.28

ERV-521

2,500

0.13

0.14

4,500

0.45

0.32

ERV-581

4,500

0.17

0.15

5,500

0.30

0.24

ERV-522

6,000

0.15

0.14

9,000

0.40

0.25

ERV-582

9,000

0.13

0.16

12,000

0.45

0.27

Advertising