6 adjusting the regulator (natural gas only), 7 engine governor adjustment – Generac Power Systems 04390-1 User Manual

Page 14

Advertising
background image

12 Generac

®

Power Systems, Inc.

2.6

ADJUSTING THE REGULATOR
(NATURAL GAS ONLY)

Although the generator has been factory set to pro-
vide maximum power, it may be necessary in some
areas to adjust this setting. Because natural gas has
different BTU or power content across the country
the engine may not perform as designed.

If experiencing engine problems at high or full load
conditions follow these steps. It will require a fre-
quency meter to perform this procedure.

1. Turn off utility power to the main distribution

panel in the house. This can be done by switching
the service main breaker to the off or open posi-
tion.

2. Allow the generator to start. Before loading the

generator, confirm that the No Load Frequency,
with the roof open and door off, is set to 63-63.5
Hz. Transfer load to emergency circuits.

3. Turn on appliances, lights, pumps, etc., that are

on the emergency circuits in an attempt to fully
load the generator. Be cautious not to overload
the generator. Use the following chart as a guide:

4. When full load has been achieved. Connect a fre-

quency meter to the output lugs of the generator’s
main line circuit breaker.

5. The fuel regulator is fitted with one (7 kW), or two

(12 & 15 kW) adjustment screws. While watching
the frequency meter, slowly turn the adjustment
screws clockwise or counterclockwise one at a
time until the highest frequency is read on the
meter. Only limited adjustment is available
between the set pins (7 kW only). Under no cir-
cumstances should any of the pins be removed
(Figures 2.1 and 2.2).

Figure 2.1 — Dual Fuel Regulators

6. When the highest frequency is reached maximum

power has been set. From this point turn both
adjustment screws 1/4 turn counterclockwise.
The regulator is now set.

Figure 2.2 — Placement of Regulator

7. Turn utility power to the main distribution panel

back on. This can be done by switching the serv-
ice main breaker to the on or closed position.
Allow the generator to shut down.

Do not make any unnecessary adjustments.
Factory settings are correct for most applica-
tions. However, when making adjustments, be
careful to avoid overspeeding the engine.

If this procedure or equipment are not available to
you, locate the nearest Generac Guardian Dealer
nearest and they can perform the adjustments.

NOTE:

A service fee may be charged for this adjustment.

2.7

ENGINE GOVERNOR ADJUSTMENT

If both AC frequency and voltage are correspondingly
high or low, adjust the engine governor as follows:

2.7.1

7 KW UNITS

1. Loosen the governor clamp bolt (Figures 2.3).
2. Hold the governor lever at its wide open throttle

position, and rotate the governor shaft clockwise
as far as it will go. Then, tighten the governor
lever clamp bolt to 70 inch-pounds (8 N-m).

3. Start the generator; let it stabilize and warm up

at no-load.

4. Connect a frequency meter across the generators

AC output leads.

!

Adjustment Screw

410

Adjustment
Screw

(One Side
Only)

Set
Pins

990

Adjustment
Screw

(Both sides)

Section 2 — Post Installation Start-up and Adjustments

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

Unit

120 Volts

240 Volts

7 kW

50.0 amps

25.0 amps

12 kW

100.0 amps

50.0 amps

15 kW

108.3 amps

54.1 amps

Advertising