1 fuse, 2 checking the engine oil level, 1 approximate crank cycle times – Generac Power Systems 04390-1 User Manual

Page 19: 4 overspeed, Oil dipstick and fill, Figure 4.1 – generator control panel

Advertising
background image

Generac

®

Power Systems, Inc.

17

NOTE:

If the fault is not repaired, the overcrank feature
will continue to activate.

3.7.3.1 Approximate Crank Cycle Times

• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds

Approximately 90 seconds total

3.7.4

OVERSPEED

This feature protects the generator from damage by
shutting it down if it happens to run faster than the
preset limit. This protection also prevents the gener-
ator from supplying an output that could potentially
damage appliances connected to the generator
circuit. Contact the nearest Generac/Guardian
Authorized Dealer if this failure occurs.

4.1

FUSE

The generator panel’s 15 amp fuse (Figure 4.1) pro-
tects the DC control circuit against overload. The fuse
is wired in series with the battery output lead to the
panel. If the fuse element has melted open, the engine
cannot crank or start. Replace the fuse using only an
identical 15-amp replacement.

The generator panel’s 5 amp fuse protects the battery
charge circuit against overload. If the fuse element
has melted open, there will not be battery charging
capabilities. Replace the fuse using only an identical
5 amp replacement. To remove fuse, push cap down
and rotate counterclockwise.

Figure 4.1 – Generator Control Panel

4.2

CHECKING THE ENGINE
OIL LEVEL

For oil capacities, see “Specifications,” Section 1.5.
For engine oil recommendations, see Section 4.3.1.
To check the engine oil level, proceed as follows
(Figures 4.2 and 4.3):

1. Start the generator by moving the Auto/

Off/Manual switch to the MANUAL position. Allow
it to run for a short while and then shut it down
by moving the switch to the OFF position.

2. Remove the dipstick and wipe it dry with a

clean cloth.

3. Install the dipstick; then, remove it again. The oil

level should be at the dipstick “Full” mark. If nec-
essary, add oil to the “Full” mark only. DO NOT
FILL ABOVE THE “FULL” MARK.

Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.

4. Install the dipstick.
5. Reset the Auto/Off/Manual switch to its original

position.

Figure 4.2 — Oil Dipstick and Fill, 7 kW

Figure 4.3 — Oil Dipstick and Fill,

12 kW and 15 kW

Oil Dipstick

Oil Fill

Oil Dipstick and Fill

!

HIGH TEMP.

OVER SPEED

LOW OIL

SYSTEM SET

OVER CRANK

MAN.

SET

OFF

AUTO

15A

FUSE

EXERCISE

TIME

R

POWER SYSTEMS, INC.

L o c a t e y o u r

n e a r e s t

d e a le r

a t :

R

FUSE

5A

E X E R C IS E R

N O T

S E T

N O

U T IL IT Y

S E N S E

4

F L A S H IN G R E D

L E D S =

F L A S H IN G G R E E N

L E D =

‹

Section 4 — Maintenance

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

Advertising