Installation, Removing from storage, System identification tags – Greenheck Fan Vektor-CD Direct or Belt Drive The Vektor-CD fan 47555 User Manual

Page 3: Standard fan configurations

Advertising
background image



Vektor-CD Centrifugal Laboratory Exhaust

®

REMOVING FROM STORAGE

As fans are removed from storage to be installed
in their final location, they should be protected and
maintained in a similar fashion, until the fan equipment
goes into operation.
Prior to assembly and installation of the Vektor fan
and system components, inspect the fan assembly to
make sure it is in working order.
1. Check all fasteners, set screws on the fan, wheel,

bearings, drive, motor base and accessories for
tightness.

2. Rotate the fan wheel(s) by hand and assure

no parts are rubbing. Access to the wheel is
obtained through a bolted panel located on the
side of the fan housing.

3. Ensure proper wheel settings for radial gap and

alignment. Refer to page 13.

Installation

Installations with inlet or discharge configurations that
deviate from this standard may result in reduced fan
performance. Restricted or unstable flow at the fan
inlet can cause pre-rotation of incoming air or uneven
loading of the fan wheel yielding large system losses
and increased sound levels.

System Identification Tags

Vektor fan systems may arrive in component pieces
due to shipping restrictions. Individual components
of a system have matching identification tags
which should be used to identify and assemble the
complete system.
Assembling systems
with different
identification tags
can cause reductions
in the fan(s)
performance.

Standard Fan Configurations

The following illustration identifies a typcial
configuration of the Vektor-CD system. Greenheck
also supplies custom configurations. Your system
may not be depicted in the drawing shown. Refer to
submittal drawing.

Lifting
Lugs

Lifting
Lugs

Gasketing

Spreader Bar

Chains

Chains

Bypass Air
Plenum

Roof Curb / Structural Support

Vektor-CD Arrangements

Rigging / Assembly Instructions

1. Use standard lifting and rigging practices.
2. All lifting lugs on each component must be utilized

at the same time.

3. Plenum, blower, and windband are to be kept level

during installation.

Vektor-CD

Single Fan System

Vektor-CD

Opposed Fan System

Vektor-CD

Dual Fan System

Vektor-CD

Triple Fan System

FW

ISOLATOR

WINDBAND

NOZZLE

FAN

FH

FLEX CONNECTOR

ISOLATION
DAMPER

PLENUM

CURB SQR

PRIMARY INLET

OPTIONAL
ROOF CURB

FL



Vektor-CD Centrifugal Laboratory Exhaust

®