Specifi cations, Centrifugal upblast roof exhaust fans – Greenheck Fan H-CUBE. User Manual

Page 7

Advertising
background image

®

Specifi cations

Centrifugal Upblast Roof Exhaust Fans

H-CUE — Direct Drive

Model H-CUE spun aluminum exhaust fans shall be centrifugal direct driven type. The fan wheel shall be backward inclined,
constructed of aluminum and shall include a wheel cone carefully matched to the inlet venturi for precise running tolerances.
Wheels shall be statically and dynamically balanced. The fan housing shall be uniquely spun from a cylinder of heavy gauge
aluminum and mounted to a high strength steel frame. The windband shall be one piece and 100% continuously robotically
welded to the one piece aluminum curb cap. High wind load braces shall connect the curb cap to the windband.

Motors shall be heavy duty ball bearing type, carefully matched to the fan load, and furnished mounted to the steel drive
assembly at the specified voltage, phase, and enclosure. Motors or drive assembly shall be mounted on vibration isolators. Fresh
air for motor cooling shall be drawn into the motor compartment through a breather tube free of discharge contaminants. Motors
shall be readily accessible for maintenance.

A disconnect shall be NEMA rated and factory installed with wiring included from the fan motor to a junction box installed within
the motor compartment. A conduit chase shall be provided through the base to the motor compartment for ease of electrical
wiring.

All fans shall bear the AMCA Certified Ratings Seal for sound and air performance.

Each fan shall bear a permanently affixed manufacturer’s engraved nameplate constructed of aluminum and containing the model
number and individual serial number for future identification.

Fans shall meet all Greenheck wind load standards and shall contain the following third party certifications:

Licensed P.E. calculations shall be available for fan per ASCE 7-02 Minimum Design Loads for Buildings and Other
Structures for exposure class C, 60 foot building height, and a type II building.

Fan shall be tested in accordance with ASTM E330-02. Structural Performance of Exterior Windows, Doors, Skylights, and
Curtain Walls by Uniform Static Air Pressure Difference at the ASCE 7-02 calculated design load.

Licensed P.E. calculations for attachment of fan to curb shall be available for ASCE 7-02 determined design pressure.

All calculations and testing shall be done by a state licensed P.E., and a certified test lab.

Fans shall be Greenheck models H-CUE or H-CUE-HP manufactured by Greenheck Fan Corporation in Schofield, Wisconsin.

H-CUBE — Belt Drive

Model H-CUBE spun aluminum exhaust fans shall be centrifugal belt driven type. The fan wheel shall be centrifugal backward
inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running
tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be uniquely spun from a cylinder of heavy
gauge aluminum and mounted to a high strength steel frame. The windband shall be 100% continuously robotically welded to the
one-piece aluminum curb cap. High wind load braces shall connect the curb cap to the windband.

Motors shall be heavy-duty ball bearing type, carefully matched to the fan load, and furnished mounted to the steel drive frame
at the specifi ed voltage, phase, and enclosure. Drive frame assembly shall be constructed of heavy gauge steel with engineered
forms for added strength. Motors and drives shall be mounted on vibration isolators with no metal to metal contact, out of the
airstream. Fresh air for motor cooling shall be drawn into the motor compartment through a ten square inch breather tube free of
discharge contaminants. Motors and drives shall be readily accessible for maintenance.

Precision ground and polished fan shafts shall be mounted in pillow block ball bearings. Bearings shall be selected for a minimum
(L10) life in excess of 100,000 hours (L50 average of 500,000 hrs) at maximum cataloged operating speed. Drives shall be sized
for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and
motor shafts.

Motor pulleys shall be adjustable for fi nal system balancing. A disconnect switch shall be NEMA rated and factory installed with
wiring included from the fan motor to a junction box installed within the motor compartment. A conduit chase shall be provided
through the base to the motor compartment for ease of electrical wiring.

All fans shall bear the AMCA Certified Ratings Seal for sound and air performance.

Each fan shall bear a permanently affi xed manufacturer’s engraved metal nameplate containing the model number and individual
serial number for future identifi cation.

Fans shall meet all Greenheck wind load standards and shall contain the following third party certifi cations.

Licensed P.E. calculations shall be available for fan per ASCE 7-02 Minimum Design Loads for Buildings and Other Structures
for exposure class C, 60 foot building height, and a type II building.

Fan shall be tested in accordance with ASTM E330-02. Structural Performance of Exterior Windows, Doors, Skylights and
Curtain Walls by Uniform Static Pressure Difference, at the ASCE 7-02 calculated design pressure.

Licensed P.E. calculations for attachment of fan to curb shall be available for ASCE 7-02 determined design pressure.

All calculations and testing shall be done by a state licensed P.E., and a certifi ed test lab.

Fans shall be Greenheck models H-CUBE, H-CUBE-HP and H-CUBE-XP manufactured by Greenheck Fan Corporation in
Schofi eld, Wisconsin.

7

Advertising
This manual is related to the following products: