4.1 Transport

NOTE: Transport the UPS only in upright position. Check for sufficient floor and elevation loading

capacity. Move the UPS in its original package to the final destination room. Do not stack other

package on top.

4.2 Unpacking

Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to

the pallet. Remove the UPS from the pallet.

BE CAREFUL!

Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS

from the pallet! Never try to lift the unit by yourself!

The UPS is equipped with castors, which allow easy displacement of the unit. Please take appropriate

measures to avoid damage on vulnerable floors.

4.3 Package

Contents

The shipping box contains a LP-U UPS, a CD-ROM, an RS232 cable, a link (5/6kVA models only, see 4.5.3) a

safety guide and this manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel

Architecture, right option slot at the rear of the unit) the shipping box also contains a yellow network cable and

one bus terminator. Inspect the UPS for damage after unpacking. If any damage is present please notify the

carrier and place of purchase immediately.

4.4 Location

Please refer to section 1.3 of ‘IMPORTANT SAFETY INSTRUCTIONS’.

4.5 Installation

IMPORTANT

:

Before making any connection and switching on the LP UPS, please check the following conditions:

The voltage and frequency of your utility supply is 120/208/230/240 Vac

and 50 or 60 Hz; from the

factory the input and output of the UPS are set to 208 Vac / 60 Hz.

Be sure that the UPS is wired for the present utility voltage. This is indicated on the packaging of the

UPS, as well as at the I/O terminals.

Overcurrent protection for the AC circuit is to be provided by others.

CAUTION:

To reduce risk of fire, connect only to a circuit input/output provided with

branch circuit overcurrent protection in accordance with the National

Electrical Code, ANSI / NFPA 70, as indicated below:

UPS model

Input overcurrent protection

(Amps)

Output overcurrent protection

(Max. Amps)

Operating input voltage

120V 208V 240V 120V

(1 X)

120V

(2X)

208V 240V

LP

5-11U

35 30 40 20 25 20

LP 5-11U /120V

60

40

20

25

20

LP

6-11U

40 35 50 25 30 25

LP 6-11U /120V

70

50

25

30

25

LP

8-11U

60 45 70 35 40 35

LP 10-11U

70

60

80

40

50

40

Table 1. external input fuse value