GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

5.1 Description of Front and Rear Panel

1 LCD

screen

2x16 characters, shows UPS system data, status messages,

settings.

The language is selectable: English, German, French, Italian,

Spanish. Section 5.3.4 describes the selection procedure.

2-4 Push-buttons

With the button keypads ‘Down’ (2) and ‘Up’ (4) you can scroll

through the several screens, with keypad 'Enter/Reset' (3) a

selection is confirmed. Keypad activity is accompanied by a short

beep. If there is no keypad activity during 20 seconds the LCD

screen will return to the default screen (except for the service

screens, see section 5.3.3).

5

LED 'operation' indicates normal operation.

6

LED ‘alarm’, indicates an alarm situation, accompanied by alarm

message(s) on the display and a sounding buzzer.

See section 5.3.2 for more information.

7

Switch ‘UPS on/off’, turns on/off the complete UPS, including the

automatic bypass!

8

Circuit breaker ‘Utility on/off’, protection fuse for utility input and

battery charger.

9

Circuit breaker ‘Bypass on/off’, fuse to protect the system in case

of severe overload or short circuit in the UPS load.

10

Manual Bypass Switch:

1 = Load on UPS

2 = Load on utility

WARNING:

In position 2, if the input line is energized,

the output is also live regardless the position of the

circuit breakers ‘utility’ and ‘bypass’.

11

Cover plate, behind it:

11a Output

terminals

11b Input

terminals

12

RS232/Contact Interface Card, with:

12a

- RS232 Interface Port (see section 6.1)

- Emergency shutdown (see 4.5.1 and 6.2)

- Battery disconnected, pin 1-2 (can be used for

external signaling).

13

Free option slot for plug-in cards:

- Relay Card (see 6.3)

- SNMP Card (see 6.4)

14

Option slot for RPA (Redundant Parallel Architecture) Card. Not

available yet.

15

DC socket / connector.

16

Battery fuse holder

17 Conduit

box

18 Cable

inlet

Figure 19 :

Front and rear panel

5 - Operation

6 5 1 2 4 3

16 7

8

9

10

11

a

17

11

b

18

15 11

14
13
12

12

a