Installation instructions, Power connection chart – GE Zoneline TINSEA530JBRZ User Manual

Page 16

Advertising
background image

Installation Instructions

16

POWER CONNECTION CHART

230/208 Volt

Power Supply Kits

with Current Leakage

Wall Plug

Heater Wattage

Detection Device

Configuration

Circuit Protective Device

@ 230/208 Volts

RAK3153

Tandem

15-Amp Time-Delay Fuse or Breaker

2.55/2.09 KW

RAK3203

Perpendicular

20-Amp Time-Delay Fuse or Breaker

3.45/2.82 KW

RAK3303*

Large Tandem

30-Amp Time-Delay Fuse or Breaker

5.00/4.10 KW

230/208 Volt

Heater Wattage

Power Supply Kits

@ 230/208 Volts

Circuit Protective Device

RAK4157

2.55 KW/2.09 KW

15-Amp Time-Delay Fuse or Breaker

RAK4207

3.45 KW/2.82 KW

20-Amp Time-Delay Fuse or Breaker

RAK4307

5.00 KW/4.10 KW

30-Amp Time-Delay Fuse or Breaker

265 Volt

Heater Wattage

Power Supply Kits

@ 265 Volts

Circuit Protective Device

RAK5172

2.55 KW

15-Amp Time-Delay Fuse or Breaker

RAK5202

3.45 KW

20-Amp Time-Delay Fuse or Breaker

RAK5302*

5.00 KW

30-Amp Time-Delay Fuse or Breaker

* Not approved for use on 7000 BTUH units.

Power Cord Connections

Direct Connections

Advertising