Performance data es-40, Specifications, Leakage pressure drop – Greenheck Fan ES-40 Series User Manual

Page 2: Æp in. wg velocity operational data, Pa) fpm (m/s), Pressure drop, Leakage, In. (3mm) aluminum linkage. damper, 201 kg/m

Advertising
background image

ÆP in. wg Velocity
Operational Data

(Pa) fpm (m/s)

Blades Start to Open 0.075 (18.7) 110 (.56)
Blades Fully Open 0.30 (74.7) 1150 (5.8)

Specifications

Backdraft dampers meeting the following specifications
shall be furnished and installed where shown on plans and/
or as described in schedules. Dampers shall consist of:
6063T5 extruded aluminum channel frame (0.063 in. [1.6mm]
thick) with 2 in. (51mm) depth; blades from 0.050 in. (1.3mm)
6063T5 extruded aluminum; synthetic polycarbonate axle
bearings; damper shall be equipped with extruded vinyl blade
seals; and internal

1

/

8

in. (3mm) aluminum linkage. Damper

Velocity (fpm)

1

x 10

Pr

essur

e Loss (

In. w

.g.)

10

9

8

7
6
5

4

3

2

2 3 4 5 6 7 8 9 10

1.0

.9

.8

.7
.6
.5

.4

.3

.2

.10

.09

.08

.07
.06
.05

.04

.03

.02

x 100

2 3 4 5 6 7 8 9 10

x 1000

2 3 4 5 6 7 8 9 10

Pressure Drop

36” x 36” Damper

Leakage testing was conducted in accordance with AMCA
Standard 500-D and is expressed as CFM per sq. ft. of
damper face area. All data has been corrected to represent
standard air at 0.075 lb/ft

3

(1.201 kg/m

3

).

Leakage

36” x 36” Damper

manufacturer’s printed application and performance data
including pressure, velocity and temperature limitations
shall be submitted for approval showing damper suitable
for pressures to 2.5 in. wg (623 Pa), velocities to 2000 fpm
(10.2m/s) and temperatures to 180°F (82ºC). Testing and
ratings to be in accordance with AMCA Standard 500-D.

Basis of design is Greenheck model ES-40.

Performance data results from testing a 36” x 36” damper in
accordance with AMCA Standard 500-D using Figure 5.7A
(no duct either side). All data has been corrected to represent
standard air at 0.075 lb/ft

3

(1.201 kg/m

3

).

Leakage

Pressure Drop

Copyright © 2008 Greenheck Fan Corporation

ES-40 Rev 3 Aug 2008

Performance Data ES-40

1.0

.9

.8
.7
.6

.5

.4

.3

.2

15
10

9

8
7
6

5

4

3

2

Air Leakage in CFM/Sq. Ft.

1

2 3 4

5 6 7

8 9 10

20 30 40

50 60

70

80

90

100 150

ES

Static Pressure Difference (in. wg)

Advertising