Optional Accessories

Remote Control Panel

The remote panel is a series of junction boxes ganged together
and includes a stainless steel face plate. The remote panel is
available with a number of different alarm lights and switches to
control the unit. The remote panel ships loose and requires
mounting and wiring in the field. Refer to “Remote Panel Wiring
Schematics” (Part #461368) for instructions on wiring the remote
panel to the 24 VAC terminal strip in the energy recovery unit
control center.

The remote panel is available with the following options:

1) Unit on/off switch
2) Unit on/off light
3) 7-day time clock
4) Hand/off/auto switch
5) Time delay override
6) Exhaust air dirty filter light
7) Outdoor air dirty filter light
8) Economizer light
9) Frost control light

10) Wheel rotation sensor light

Variable Frequency Drive for Energy Recovery Wheel (GPD-305 Series by Yaskawa)

Factory installed VFD for the energy recovery wheel are
programmed at the factory per the settings shown in TABLE 4
below. Refer to the instruction manual that ships with the unit
when making adjustments. A copy of the manual can be found
online at www.drives.com. For technical support, contact Yaskawa
direct at 1-800-927-5292.

TABLE 4: Factory settings for VFD used on energy recovery wheel

VFD key pad & LCD

Parameters

Setting Comment

n01

Access Level

1

n01 - n79 can be read or set

n02

Operation Method

1

Terminal

n03

Reference Selection

2

0-10 Vdc (mod. wheel econ.)

n09

Max Frequency

60 Hz

n16

Accl Time 1

10

Seconds

n17

Decel Time 2

10

Seconds

n29

Jog Frequency

6 Hz

n30

Ref Upper Limit

100% % of n09

n31

Ref Lower Limit

0%

% of n09

n32

Motor Rated FLA

? A

n36

Multi-Function Input

10

n40

Frequency Detection

4

n41

Analog Freq. Ref. Gain

0

Inverse acting

n42

Analog Freq. Ref. Bias

99

Inverse acting

n58

Freq. Dectection Level

5.9 Hz

n01

Access Level

0

n01 read or set; n02-n79 read