Pre-installation checks, Wall opening requirements – Greenheck Fan PN 471755 User Manual

Page 3

Advertising
background image

Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply

®

3

Fan

Size

Damper

Size

Square

Recommended Wall Opening (W.O.)

Square

M

Minimum

Filtered Supply Wall Housing Only

Figures 1

and 2

Figure 3

Figure 4

A

B

C

Filter Quantity & Size

8

10 (254)

141/4 (362)

10½ (267)

-

6 (152)

-

-

-

-

10

12 (305)

161/4 (413)

12½ (318)

-

6 (152)

-

-

-

-

12

14 (356)

191/4 (489)

14½ (368)

-

7 (178)

-

-

-

-

14

16 (406)

211/4 (540)

16½ (419)

-

8 (203)

-

-

-

-

16

18 (457)

231/4 (591)

18½ (470)

-

9 (229)

-

-

-

-

18

20 (508)

251/4 (641)

20½ (521)

-

10 (254)

-

-

-

-

20

22 (559)

271/4 (692)

22½ (572)

-

12 (305)

-

-

-

-

24

26 (660)

333/4 (857)

26½ (673)

33

3

4

(857)

13 (330) 32

1

4

(819)

63 (1600)

24 (610)

4

23

1

4

x 16

1

4

(591 x 413)

30

32 (813) 393/4 (1010)

32½ (826)

39

3

4

(1010) 13 (330) 38

1

4

(972)

65 (1651)

26 (660)

4

24

5

8

x 19

1

4

(625 x 489)

36

38 (965) 453/4 (1162)

38½ (978)

45

3

4

(1162) 14 (356) 44

1

4

(1124) 67

1

4

(1708)

281/4 (718)

6

23

1

4

x 22

1

8

(591 x 562)

42 44 (1118) 513/4 (1314) 44½ (1130) 51

3

4

(1314) 15 (381) 50

1

8

(1273) 72

7

8

(1851)

34 (864)

6

24

1

8

x 25

1

8

(613 x 638)

48 50 (1270) 573/4 (1467) 50½ (1283) 57

3

4

(1467) 16 (406) 56

1

8

(1426) 72

7

8

(1851)

34 (864)

12

23

1

4

x 18

3

4

(591 x 476)

54 56 (1422) 633/4 (1619) 56½ (1435) 63

3

4

(1619) 17 (432) 62

3

8

(1584) 79

11

16

(2024) 40

11

16

(1033) 12

23

1

4

x 20

3

4

(591 x 527)

60 62 (1575) 693/4 (1772) 62½ (1588)

-

19 (483)

-

-

-

-

72 74 (1880) 843/4 (2153) 74½ (1892)

-

19 (483)

-

-

-

-

All dimensions given in inches (millimeters). Filters are 2 inch (51 mm) nominal thickness. Above filter sizes are actual dimensions.

M

W.O.

W.O.

W.O.

M

W.O.

W.O.

W.O.

Figure 1 - Wall Housing Installation

Figure 2 - Wall Collar Installation

Figure 3 - Direct to Wall Installation

Figure 4 - Filtered Supply Wall Housing Installation

M

W.O.

W.O.

W.O.

Filters

Wall
Housing

Filter
Section

INTERIOR

W

all

EXTERIOR

Optional 90º
Weatherhood

Filters

Airflow

Optional
Damper

W

all

A

C

B

24 in.

15 in.

Pre-Installation Checks

• Check chart below for correct wall opening

dimensions.

• Check motor voltage and amperage rating for

compatibility with electrical supply. Supply wiring
must be properly fused and conform to local and
national codes.

• Motor load amperage must be checked and

compared to nameplate rating to avoid serious
damage to motor when speed is increased.

Wall Opening Requirements

Wall opening size and propeller-to-damper distance
are two important dimensions for fan installation.

Fans mounted to the wall require a different wall
opening (W.O.) size than those mounted in collars or
wall housings. Propeller-to-damper distance (M) is
important to reduce turbulence and damper flutter
which may lead to premature damper failure.
Figure 1 and 2 show the wall opening (W.O.) required
for installations with either a wall housing or collar.
Figure 3 shows the recommended wall opening
(W.O.) and the minimum distance (M) suggested
between the fan and damper for direct to wall
installations.
Figure 4 shows the dimensions and wall opening
(W.O.) required for installations with a filtered supply
wall housing.