Greenheck Fan Smoke Dampers SMD-301V User Manual

Model smd-301v smoke dampers, Application, Standard construction

Advertising
background image

Model SMD-301V meets the requirements for smoke

dampers established by:
National Fire Protection Association

NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing (#3230-0981:104)

Application

Model SMD-301V is a vertical blade low leakage rated smoke

damper. High strength airfoil blades insure lowest resistance to

airflow in HVAC systems with velocities to 4000 fpm (20.3m/s) and

4 in. wg (1.0 kPa).

UL555S Leakage Rating

Leakage Class:

I

Operational Rating

Maximum Velocity:

2000 fpm (20.3 m/s) up to

100 in. x 32 in. H

(2540mm x 813mm) or

4000 fpm (20.3 m/s) up to

50 in. x 32 in. (1270mm x 813mm)

Maximum Pressure:

4 in. wg (1 kPa)

Maximum Temperature:

350ºF (177ºC)

Standard Construction

Frame:

5 in. x 1 in. (127mm x 25mm)

galvanized steel hat channel with

reinforced corners. A low profile

head and sill are used on sizes

less than 17 in. (432mm) high to

maximize free area and

performance.

Blades:

Double skin airfoil shape of

galvanized steel with full length

structural reinforcement. 14 ga.

(2 mm) equivalent thickness.

Seals:

Extruded silicone rubber blade

seals. Flexible stainless steel

jamb seals.

Linkage:

Concealed in jamb.

Axles:

1

/

2

in. (13mm) dia. plated steel.

Bearings:

304 stainless steel

Size Limitations:

Minimum Size:

6 in. W x 8 in. H

(152mm W x 203mm H)

Maximum Size:

Single Section:

50 in. W x 32 in. H

(1270mm W x 813mm H)

Multiple Section:

100 in. W x 32 in. H

(2540mm W x 813mm H)

Optional Features:

• OCI (Open closed indication switches)
• Electric or pneumatic actuators to accomplish smoke

management and system functions.

• Transitions (R, C, O)
• POC retaining angles
• Momentary Switch
• Sealed transitions and sleeves

Model SMD-301V

Smoke Dampers

Steel Airfoil Blades

UL 555S Leakage Class I

*W&H dimensions furnished approximately

1

/

4

in. (6mm) undersize.

“UL CLASSIFIED (see complete marking on

product)”

“UL CLASSIFIED to Canadian safety standards

(see complete marking on product)”

Standard 555S (Listing #R13317)

W*

H*

Installation instructions available at www.greenheck.com

Advertising