GFK-2193A

Chapter 2 Installation

2-3

2

PROFIBUS Cable Types

The recommended cable is

Belden 3079A PROFIBUS Cable

This is a shielded, 150 ohm twinaxial (single twisted pair) cable. It has 22 AWG
conductors and a mutual capacitance of 9.0 pF per foot, nominal. For complete
specifications on this cable, please contact your Belden dealer or visit their website at
www.belden.com.

Alternate cable types are:

Siemens 6XV1 830-OAH10 Two Core shielded

Siemens 6XV1 830-OBH10 w/PE Sheath

Siemens 6XV1 830-3AH10 for underground burial

Siemens 6XV1 830-3BH10 trailing cable

Bosch Comnet DP #913 548 Flexible PROFIBUS cable

Bosch Comnet DP #917 201 Trailing PROFIBUS Cable

Bosch Comnet DP #917 202 Massive PROFIBUS Cable

Note: Allen Bradley “blue hose,” which has an impedance of 78 ohms, is not

recommended for this application.

Network Termination

Termination resistors are needed, as defined in DIN 19245 Part 1 section 3.1.2.5.

Master

Slave

Slave

Slave

Slave

Slave

Termination Required

(Segment 1)

One terminator must be applied at each end of a network segment.

Master

Slave

Slave

Slave

Slave

Slave

Repeater

Term ination Required

(Segm ent 1)

Term ination Required

(Segm ent 2)

Generally, termination is provided in commercially-available PROFIBUS standard network
connectors. Some connector vendors provide termination capability in the connector and
a switch on the connector to enable/disable termination. Some connector vendors provide
both terminated and unterminated connectors.