7.2.4

Shutdown of a single unit in a parallel system


With purpose to separate one unit from the parallel system.


1. Switch OFF the inverter only on this unit entering the screen:

MENU/COMMAND MENU/INVERTER OFF
Attention
: to switch OFF permanently the inverter the key

Enter must be pressed 2 times.

COMMAND MENU

INVERTER ON
INVERTER OFF *


2. Switch OFF the output switch Q1 (0) only on this unit.


3. Perform the command total off only on this unit.

4. Switch OFF battery breaker only from battery cabinet belongs to this unit.

5. In order to discharge the DC link capacitors, start once more

the inverter only on this unit through the screen:
MENU/COMMAND MENU/INVERTER ON

COMMAND MENU

INVERTER ON *
INVERTER OFF

Remark: command

INVERTER ON will be enabled only when

the inverter voltage of each phase decreases
below 7 VAC (about 30 seconds).

INVERTER: U1=

7V

U2= 7V U3= 7V
Frequency = 60.0Hz

Synchronized

Before proceeding to step 6, check on the display panel that
the DC link voltage (both polarities) Udcp and Udcn has reached
the minimum voltage of 5 VDC (about 30 seconds).

Udcp= 5V Udcn=

5V

Ubp=0V

Ubn=0V O

Charge level

= 0%

Autonomy =

0min


6. Switch OFF the inverter only on this unit entering the screen:

MENU/COMMAND MENU/INVERTER OFF

COMMAND MENU

INVERTER ON
INVERTER OFF *


7. Switch OFF the mains power only on this unit at the AC input distribution panel.

END OF PROCEDURE


WARNING !

In case the unit should be disconnected and removed from the operating system, the
operation must be performed by qualified persons.
If an intermediate unit must be disconnected from a parallel system pay attention
do not open the control bus: keep the plugs J3 and J4 connected to the board “P16 -
Connector adapter RPA” (see Section 4.8.4)
.