Greenheck Fan EM-30 Series User Manual

Backdraft damper, Em-30 series, Vertical mount - horizontal airflow extruded

Advertising
background image

Application and Design

The EM-30 series is a vertical mounted backdraft damper that is designed to
allow horizontal airflow and prevent reverse airflow. The damper is opened by
air pressure differential and closed by gravity.

Ratings

(See page 2 for specific limitations)

Pressure: 4.0 - 10.0 in. wg (996 Pa- 2491 Pa)

differential pressure.

Velocity: 2500 to 3500 fpm (13 m/s - 18 m/s)

Temperature: 180°F (82ºC)

Standard Construction

Frame: Heavy gauge 6063T5 extruded aluminum.

(0.125 in. [3.2mm] thickness)

Blades: Heavy gauge 6063T5 extruded aluminum.

(0.070 in. [1.8mm] thickness)

Axles:

3

/

4

in. (19mm) dia. metallic

Bearings: Synthetic (acetal) sleeve type

Linkage:

1

/

8

in. (3mm) plated steel

Blade Seals: Vinyl

Size Limitations

Minimum Size (without weights): 8 in. W x 8 in. H

(203mm x 203mm)

Minimum Size (with weights): 8 in. W x 11 in. H

(203mm x 279mm)

Maximum Size: 48 in. W x 74 in. H

(1219mm x 1880mm)

Options and Accessories

• Counterbalance Weights

• APC (Adjustable Pressure Controller).

Allows field setting of relief pressure on

all EM dampers. Use one per panel.

Maximum recommended pressure set

limitations are as follows:

(EM-30 damper must be equipped with counterbalance.)

Sizes larger than maximum shown will be supplied as two or

more equal size smaller dampers required to make up the size

specified. These larger multiple damper assemblies require

field assembly and may require additional reinforcement (not

supplied by Greenheck) to support the assembly.

*W & H dimensions furnished approximately

1

/

4

in. (6mm) under size.

H*

W*

EM-30 SERIES

Vertical Mount - Horizontal Airflow

Extruded

BACKDRAFT DAMPER

3

1

/

8

in.

Airflow

1

1

/

2

in.

1

1

/

2

in.

3 in.*

5 in.

11

1

/

8

in.

* Optional counterbalance weights

dimensioned (

5

/

8

in. without weights).

EM-30

No Flange

EM-31

Flange On
Discharge

EM-32

Flange On

Intake

Area ft2

(m2)

Maximum Set

Pressure

in. wg (Pa)

4 (.37)

.75 (187)

6 (.56)

.50 (125)

8 (100)

.40 (100)

10 (.93)

.30 (75)

15 (1.39)

.20 (50)

20 (1.86)

.15 (37)

24 (2.23)

.125 (31)

Counterbalance weights may require field adjustment. Instructions are
available at www. greenheck.com.

Advertising