Application and Design

The EM-40 series is a horizontally mounted backdraft damper that is designed to allow vertical airflow down and prevent
reverse airflow. The damper is opened by air pressure differential and closed by gravity. Standard models include adjustable
counterbalance weights to assist closing.

Ratings

(See page 2 for specific limitations)

Pressure: 4.0 - 10.0 in. wg (996 Pa - 2491 Pa)

differential pressure

Velocity: 2500 to 3500 fpm (13m/s - 18 m/s)

Temperature: 180°F (82ºC)

Standard Construction

Frame: Heavy gauge 6063T5 extruded aluminum.

(0.125 in.[3.2mm] thickness)

Blades: Heavy gauge 6063T5 extruded aluminum.

(0.070 in. [1.8mm] thickness)

Axles:

3

/

4

in. (19mm) dia. metallic

Bearings: Synthetic (acetal) sleeve type

Linkage:

1

/

8

in. (3mm) plated steel

Blade Seals: Vinyl

Size Limitations

Minimum Size: 8 in. W x 11 in. H

(203mm x 279mm)

Maximum Panel Size: 48 in. W x 74 in. H

(1219mm x 1880mm)

Options and Accessories

• 1

1

/

2

in. flange on discharge: EM-41

• 1

1

/

2

in. flange on intake:

EM-42

• APC (Adjustable Pressure Controller).

Allows field setting of relief pressure on

all EM dampers. Use one per panel.

Maximum recommended pressure set

limitations are as follows:

EM-40 SERIES

Horizontal Mount - Vertical Airflow Down

Sizes larger than maximum shown will be supplied

as two or more equal size smaller dampers required

to make up the size specified. These larger multiple

damper assemblies require field assembly and may

require additional reinforcement (not supplied by

Greenheck) to support the assembly.

*W & H dimensions furnished approximately

1

/

4

in. (6mm) under size.

Extruded

BACKDRAFT DAMPER

ADJUSTABLE COUNTERBALANCE

3

1

/

8

in.

Airflow

1

1

/

2

in.

1

1

2

in.

3 in.

5 in.

11

1

/

8

in.

/

EM-40

No Flange

EM-41

Flange On

Discharge

EM-42

Flange On

Intake

Area ft2

(m2)

Maximum Set

Pressure

in. wg (Pa)

4 (.37)

.75 (187)

6 (.56)

.50 (125)

8 (100)

.40 (100)

10 (.93)

.30 (75)

15 (1.39)

.20 (50)

20 (1.86)

.15 (37)

24 (2.23)

.125 (31)

Counterbalance weights may require field adjustment. Instructions are
available at www. greenheck.com.

W*

H*