5 connecting start circuit wires – Generac 4678-1 User Manual

Page 6

Advertising
background image

4

Generac

®

Power Systems, Inc.

Before connecting wiring cables to terminals, remove

any surface oxides from the cable ends with a wire

brush. If ALUMINUM conductors are used, apply joint

compound to conductors. After tightening terminal

lugs, carefully wipe away any excess joint compound.
All power cables should enter the switch next to trans-

fer mechanism terminals.
Connect power source load conductors to clearly

marked transfer mechanism terminal lugs as follows

(Figure 2.3).
1. Connect NORMAL (utility) power source cables to

switch terminals N1 and N2.

2. Connect STANDBY source power cables to transfer

switch terminals E1 and E2.

3. Connect customer LOAD leads to switch terminals

T1 and T2.

Conductors must be properly supported, of approved

insulative qualities, protected by approved conduit, and

of the correct wire gauge size in accordance with appli-

cable codes.
Tighten the wire into lugs to the following torque:
• 100 Amp Switch: 50 Inch-Pounds
Make sure to maintain proper electrical 1/2 inch clear-

ance between live metal parts and grounded metal.

2.5 CONNECTING

START

CIRCUIT

WIRES

Control system interconnections (Figure 2.3) consist of

UTILITY 1 and 2. LOAD 1 and 2; and leads 23 and 194.

Control system interconnection leads must be run in a

conduit that is separate from the AC power lead.

Recommended wire gauge sizes for this wiring depends

on the length of the wire, as recommended below:

Section 2 — Installation

Generac 100 Amp Transfer Switch

Figure 2.3 — Transfer Switch Interconnections (Drawing No. C3921)

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE

SIZE

460 feet (140m)

No. 18 AWG.

730 feet (223m)

No. 16 AWG.

1,160 feet (354m)

No. 14 AWG.