IDENTIFICATION RECORD

DATA LABEL

Every generator set has a DATA LABEL that contains
important information pertinent to the generator. The
data label, which can be found attached to the gen-
erator’s lower connection box, lists the unit’s serial
number and its rated voltage, amps, wattage capacity,
phase, frequency, rpm, power factor, etc.

WAUKESHA, WI

RATED KW

RATED VOLTAGE

POWER FACTOR

ENGINE RPM

ALTERNATOR SUBTRANSIENT REACTANCE

ALTERNATOR TRANSIENT REACTANCE

CLASS

MODEL

MADE IN USA

PRODUCTION DATE

GENERAC POWER SYSTEMS, INC.

HERTZ

RATED KVA

GENERATOR SET DATA

RATED AMPS

ALT RPM

PHASE

SERIAL

ROTOR

STATOR

WINDING INSULATION AT 25

°C AMBIENT

NOTE:

For actual information related to this particular
model, please refer to the Manual Drawing Listing
located at the end of this manual, or to the data
label affixed to the unit.

Generator Model and Serial Number

This number is the key to numerous engineering and
manufacturing details pertaining to your unit. Always
supply this number when requesting service, order-
ing parts or seeking information.

‹



Identification Code

Use this code to obtain important information about
the generator. For example, if the code is:

M — Designates generators capable of paralleling.

NOTE: Only 100kW and 150kW, 6.8L units
are currently available for this configura-
tion.

QT — Quiet Test Generator Series
100 — kw Rating
5.4 — Engine Size in Liters
A — Voltage Code: A = 120/240, Single-phase;

G = 120/208, Three-phase; K = 277/480,
Three-phase; J = 120/240, Three-phase;
L = 346/600, Three-phase

N — Fuel: N = Natural Gas; V = Vapor Propane
S — Enclosure Material: A = Aluminum; S

= Steel (Corrosion Resistant Aluminum
Enclosure Material, Steel is Standard)

N — Emission Equipment: N = No Equipment;

Y = Catalytic Converter and Air/Fuel Ratio
Controller

A — Industrial Dealer Product

Voltage Codes

The identification code letter following the unit’s
engine size is the generator’s “voltage code.”

Groups and Assembly Numbers

The manual drawing listing lists the groups and cor-
responding assembly numbers for each unit. The
assembly numbers refer to exploded view drawing
numbers that are applicable to the specific generator
model. These drawings are located in the back half
of this manual.







2-1

Standby Generator Sets

General Information

Identy001 Rev.

C 04/06

M Q T 1 0 0 5 4 A N S N A