OM-884 Page 13

2-9.

24-Socket Receptacle RC17 Information

Socket*

Socket Information

A

Provides connection to 2TA; for customer use.

B

Current Detect output to robot control unit with respect to Socket D; isolated CR1 contacts rated
1A at 120 VAC.

D

Current Detect output to robot control unit with respect to Socket B; isolated CR1 contacts rated
1A at 120 VAC.

E

Contactor Control; +24 volts dc input from robot control unit with respect to Socket J (Circuit
Common).

F

Jog Forward; +24 volts dc input from robot control unit with respect to Socket J (Circuit
Common).

G

Gas Control; +24 volts dc input from robot control unit with respect to Socket J (Circuit Common).

H

Wire Stick Check; +24 volts dc input from robot control unit with respect to Socket J (Circuit Com-
mon).

J

Circuit Common for Sockets E, F, G, and H; all circuit voltages referenced to this point.

B

C

D

E

G

J

F

H

A

K

Jog Forward; momentary contact output to robot control unit with respect to Socket Q (Digital
Common).

M

N

L

R

S

K

P

T

Q

U

V

L

Set-Up and Weave Set-Up output to robot control unit with respect to Socket Q (Digital Common).

R

S

T

U

V

W

X

Y

Z

M

Weave Set-Up output to robot control unit with respect to Socket Q (Digital Common).

S-0291

N

Wire Stick Signal output to robot control unit with respect to Socket Q (Digital Common); indicates
wire is stuck to work; isolated CR2 contacts rated 1A at 120 VAC.

P

Weld Standby output to robot control unit with respect to Socket Q (Digital Common); indicates
robot interface is in standby; isolated CR5 contacts rated 3A at 120 VAC.

Q

Digital Common for Sockets K, L, M, N, and P.

R

+ Peak Amps; 0-10 volts dc input from robot control unit with respect to Socket S (analog
common) equals 0-500 amperes dc output.

S

Peak Amps; analog common for Socket R (+ Peak Amps).

W

Wire Feed Speed; analog common for Socket X (+ Wire Feed Speed).

X

+ Wire Feed Speed; 0-10 volts dc input from robot control unit with respect to Socket W (analog
common) equals 0-1000 IPM.

Y

Arc Volts; analog common for Socket Z (+ Arc Volts).

Z

+ Arc Volts; 0-10 volts dc input from robot control unit with respect to Socket Y (analog common)
equals 0-50 volts dc output.

*The remaining sockets are not used.