Before Calling for Service

Section 5

Safety Limit #1
Freeze time exceeds 60 minutes for 3 consecutive freeze cycles.

Possible Cause

Check/Correct

Improper installation

• See “Installation Instructions” Section two of this manual

Water system

• Low water pressure (20 psi minimum.)

• High water pressure (80 psi maximum.)
• High water temperature (90°F/32.2°C maximum.)

• Clogged water distribution tube

• Dirty/defective water float valve
• Loss of water from sump area

• Defective water pump

Electrical system

• Ice thickness probe out of adjustment

• Harvest cycle not initiated electrically
• Relay not energizing

• Compressor electrically non-operational

Restricted condenser air flow

(air-cooled models)

• High inlet air temperature (110°F/43.3°C maximum.)

• Condenser discharge air recirculation

• Dirty condenser filter
• Dirty condenser fins

• Defective fan cycling control

• Defective fan motor

Refrigeration system

• Non-Manitowoc components
• Improper refrigerant charge

• Defective hot gas valve

• Defective compressor
• TXV starving or flooding (check insulation and bulb mounting)

• Non-condensables in refrigeration system

• Plugged or restricted high side refrigerant lines or component


Safety Limit #2
Harvest time exceeds 3.5 minutes for 3 consecutive harvest cycles.

Possible Cause

Check/Correct

Improper installation

• See “Installation Instructions” Section two of this manual

Water system

• Water area (evaporator) dirty
• Water freezing behind evaporator

• Low water pressure (20 psi min.)

• Loss of water from sump area
• Clogged water distribution tube

• Dirty/defective water float valve

• Defective water pump

Electrical system

• Ice thickness probe out of adjustment
• Ice thickness probe dirty

• Bin switch defective

• Premature harvest

Refrigeration system

• Non-Manitowoc components
• Improper refrigerant charge

• Defective hot gas valve

• TXV flooding (check insulation and bulb mounting)
• Defective fan cycling control

Because there are many possible external problems,

do not limit your diagnosis to only the items listed in these charts.