Sg1400C3 STudio generaTor • operaTion manual — rev. #0 (10/05/11) — page 25

CaMLOk/vOLtaGE OutPut PanEL

The definitions below describe the controls and functions

of the Camlok/Voltage Output Panel (Figure 7).
1.

CB4/CB5 Circuit Breakers — These circuit breakers

protect the 120 VAC auxiliary output receptacles from

overload.

2.

CB6/CB7 Circuit Breakers — These circuit breakers

protect the bates output receptacles from overload.

3.

generator voltage Test points — To determine if

the generator's output voltage is present and correct,

connect a test meter to these test points during

troubleshooting and maintenance.

4.

paralleling Cable in — This Ethernet input connection

point is used when multiple generators are going to be

connected.

5.

paralleling Cable out — This Ethernet output

connection point is used when multiple generators are

going to be connected.

6.

BuS Hot indicator lamp — When lit, this indicator

lamp informs that the voltage bus is active (high

voltage).

never connect or disconnect cables from

the camlok or auxiliary receptacles when this indicator

is

on. The possibility exists of electrocution, shock or

even death if cables are connected or unplugged when

this indicator is lamp lit.

7.

120 vaC output receptacles — These 15-amp

receptacles provide 120 VAC output. The maximum

allowable combined amps (both receptacles) is 25 amps

when the voltage selector switch in the 3

Ø

277/480 VAC

position.

8.

Bates 120vaC output receptacles — These

receptacles provide AC voltage output. Each receptacle

is protect by a 100 amp breaker. These receptacles

cannot be used when the voltage selector switch is in

the 3

Ø

277/480 VAC position.

9.

Camlok receptacles — These output voltage

connection points (6 pairs) are used for load connection.

alWaYS pay close attention when connecting and

disconnecting power cables from these camlok

receptacles. The possibility exists of electrocution,

shock or even death if cables are connected or

unplugged when the bus hot indicator lamp is lit.

3

4

5

6

7

7
8

8

GREEN

WHITE

RED

BLUE

BLACK

9

1 2

Figure 7. Camlok/Voltage Output Panel