StartuP

BeFore STarTing

1. Place the Control Power switch (Figure 18) on the

digital control panel in the up position (ON).

Figure 18. Control Power Switch (ON)

2. Place the voltage selector switch (Figure 19) in the

desired voltage setting position. The corresponding

Voltage Status LED on the control panel will light to

indicate the selected voltage (Figure 20).

Figure 19. Voltage Selector Switch

120/208 3Ø Position

Figure 20. Voltage Status LEDs

3. If it is necessary to prime engine before starting (such

as after changing fuel filter or running out of fuel), place

the fuel valves in the prime position (Figure 21). Place

the fuel priming switch (Figure 22) in the up position.

CauTion

The engine’s exhaust contains harmful emissions.

alWaYS have adequate ventilation when operating.

ON (UP)

120/208

277/480

120/240

3

1

3

LIGHTS IF

SELECTED

Figure 21. Fuel Valves (Prime Mode)

Figure 22. Fuel Priming Switch (ON)

4. After priming is complete, release the fuel priming

switch. Place the fuel valves in the run mode (Figure

23).

Figure 23. Fuel Valves (Run Mode)

5. Verify that all three circuit breakers (Figure 24)are in

the

on position prior to starting the engine.

Figure 24. Circuit Breakers (ON)

FUEL VALVES IN

PRIME MODE

ON (UP)

FUEL VALVES IN

RUN MODE

Electronic Trip Unit

Instantaneous Trip Setting - Amps

Push to Trip

Test

Status

A — 500

B — 600

C — 800

D — 1000

E — 1250

F — 1500

G — 2000

H — 2500

E

D

C

B

A

H

G

F

450 AMP

LONG — INST.

ON

VERIFY CIRCUIT

BREAKERS ARE ON