624WBPF Woodburning Fireplace

53D9052

Survey the planned location for the fireplace for overhead plumbing or electrical wires, etc., that
might complicate the installation or endanger persons installing or cleaning the chimney. Avoid
a location where the chimney cap will be near abrupt changes in the roof shape, nearby wall or
embankments, under or near trees or above the roof of a single story wing of a two story building.
Figure 6. All these conditions can cause turbulence or pressure conditions that can cause poor
chimney draft and smoke spillage from the fireplace opening. Elbows may be used to offset the
chimney to avoid obstructions or to locate the chimney cap in a preferred location. Refer to the
sections of this manual pertaining to chimney offsets for instructions on proper elbow usage. Poor
installation or location of the chimney cap and/or components can cause wind blown rain to enter
the chimney.
If the fireplace is to be installed on an outside wall, the surrounding walls (chase) should be insu-
lated. Failure to insulate the fireplace from outside temperatures will cause heat loss through and
around the fireplace.

iNStallatioN PreParatioN

14’ Min.

FP2347
single story install

Chimney Cap

Single Story installation with attic Space

Storm Collar

Flashing

Flue Outlet Height

3’ Min. or 2’ Above
any Point within 10’

See Table
1 for Roof
Opening Size

Attic Space

Firestop Spacer
(1Z\x” Air space
Clearance to
Combustibles)

Chimney
Sections

17” Square
Opening in
Joist

FP2347

Figure 4

2” Min. Air Space
Clearance Between
Combustibles and
Chimney

FP1882
chimney location
8/08

Preferred
Location

Poor
Location

FP1882

Figure 6

3 ft. Min. 

FP2348
multistory install

Multiple Story installation

Chimney Cap

Storm Collar
(Included with
cap)

Flashing

Refer to Table
1 for Roof
Opening Size

Attic Space

Firestop

Spacer (2”

Air Space

Clearance to

Combustibles)

2” Clearance to

Combustibles (Min.)

17” Square Open-
ing in Joist

Max. instal-

lation height

-

86 ft.

Support re-

quired every

35 ft.

Third Floor
Area

Second
Floor Area

First Floor
Area

Flue Outlet Height

17” Square
Opening in
Joist

17” Square
Opening in Joist

Firestop

Spacer

Firestop

Spacer

FP2348

Figure 5