Marathon monitors inc – Marathon Computer AACC 2000 User Manual

Page 84

Advertising
background image

Marathon Monitors Inc.

AACC 2000 Carbon Nov. 1, 1997

84

Select ‘

YES’ with

or

YES

Start calibration

Wait for calibration to

buSy

Busy calibrating

complete.

donE

PV input calibration completed

FAIL

Calibration failed

Note. When a DC input module is installed for the first time, or there is a requirement to change one,
then the microprocessor in the controller needs to read the factory calibration data stored in the module.
Select ‘

FACt’ as the calibration value. Step to ‘GO’ and start calibration.

DC Output Calibration

The following parameters apply to DC output modules ie for

rcAL = 1A.Hi to 3A.Lo

cAL.H

Output Calibration High

0

0 = Factory set calibration.
Trim value until output = 9V, or
18mA

cAL.L

Output Calibration Low

0

0 = Factory set calibration.
Trim value until output = 1V, or
2mA

User calibration

UCAL

User calibration enable

Yes/no

pt1.L

Low calibration point for Input 1

The factory calibration point at which the
low point offset was performed.

pt1.H

High calibration point for Input 1

The factory calibration point at which the
high point offset was performed.

OF1.L

Offset Low for Input 1

Calculated offset, in display units.

OF1.H

Offset High for Input 1

Calculated offset, in display units.

pt2.L

Low calibration point for Input 2

The factory calibration point at which the
low point offset was performed.

pt2.H

High calibration point for Input 2

The factory calibration point at which the
high point offset was performed.

OF2.L

Offset Low for Input 2

Calculated offset, in display units.

OF2.H

Offset High for Input 2

Calculated offset, in display units.

Name

Description

Values

Meaning

PASS

PASS

Password configuration

ACC.P

FuLL or Edit level password

cnF.P

Configuration level password

Exit

Exit

Exit configuration

no/YES