AACC 2000 Carbon Nov. 1, 1997

91

Select High-point Calibration

This is the Calibration Status display, again.

Use

/

to select the parameter for the High-point

Calibration of Input 1, ‘

ip1.H’.

Press

Adjust High-point Calibration

This is the display for adjusting the High Calibration point of
Input 1. The lower readout is a live reading of the process
value, which changes as the input changes.

Feed the desired high-point calibration signal to the
controller, from the calibration source. If the lower readout
does not show this value, then use

/

to adjust the

reading to the required value.

Press

to return to the ‘

ip-List’ header.

To protect the calibration against unauthorised adjustment
return to Operator level and make sure that the calibration
parameters are hidden. Parameters are hidden using the
‘

Edit’ facility described in Chapter 3.

To perform a User Calibration on Input 2, proceed as with
Input 1 above, except that when ‘

CAL.S-nonE’ appears,

press

/

until ‘

CAL.S-iP2.L’ is obtained, then

proceed as with Input 1. Repeat the procedure for ‘

iP2.H’