C. DRYER ENCLOSURE REQUIREMENTS

Bulkheads and partitions should be made of noncombustible materials and must be located a minimum of 12-
inches (30.48 cm), 18-inches (45.72 cm) or more is recommended for ease of installation, maintenance, and
service) above the dryer outer top, except along the front of the dryer which may be partially closed in if desired.
The clearance between the bulkhead header and the dryer must be a minimum of 4-inches (10.16 cm) and must
not
extend more than 4-inches (10.16 cm) to the rear of the front. The bulkhead facing must not be closed in
ALL the way to the top of the dryer. A 1-inch (2.54 cm) clearance is required.

NOTE: Allowances must be made for opening the control door.

Dryers may be positioned sidewall to sidewall. However, a 1/16” (1.58 mm) minimum allowance must be made
for opening and closing of the control door and the lint door. It is suggested that the dryer be positioned about 30-
inches (76.2 cm) away from the nearest obstruction for ease of installation, maintenance, and service (to be
measured from the back guard.) (Refer to the illustration above for details.)

NOTE: Air considerations are important for proper and efficient operation.

IMPORTANT: For overhead clearance, even though a minimum of only 12-inches (30.48 cm) is

required, 18-inches (45.72 cm) or more is suggested. The additional clearance is
advantageous for ease of installation and service.

IMPORTANT: When fire sprinkler systems are located above the dryers, a minimum of 18-inches

(45.72 cm) above the dryer console (module) is required. Dryers may be positioned
sidewall to sidewall however, a 1/16-inch (1.58 mm) minimum allowance is required
between dryers (or wall) for ease of installation and maintenance. Allowances must
be
made for the opening and closing of the control door and the lint door.