3-11. Electrical Service Guide

Input Voltage

230

460

575

Input Amperes At Rated Output

69

34.5

27.5

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

80

40

30

Normal Operating 3

100

50

40

Min Input Conductor Size In AWG 4

4

8

10

Max Recommended Input Conductor Length In Feet (Meters)

237

(72)

422

(129)

444

(135)

Min Grounding Conductor Size In AWG 4

8

10

10

Reference: 1999 National Electrical Code (NEC)

1 Consult factory for circuit breaker applications.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

3-12. Placing Jumper Links

Ref. 800 103-A

Y

Disconnect and lockout/tag-
out input power before
installing or moving jumper
links.

Check input voltage available at
site.

1

Jumper Link Label

Check label − only one is on unit.

2

Jumper Links

Move jumper links to match input
voltage.

Close and secure access door, or
go on to Section 3-13.

Tools Needed:

2

1

Do not overtighten
jumper link nuts.

230 VOLTS

Ref. S-174 973-A

575 VOLTS

460 VOLTS

3/8 in

3/8 in