Comet installation and user manual: E-6761200XT/FC

2.5

Merlin Gerin by MGE UPS SYSTEMS

Connection sequence for Comet other than 5kVA:

remove the connection cover panel 13 that is secured with screws;

connect the AC input cables to Mains 1 terminal block XR1, carefully

respecting earth, neutral and phase correspondence as indicated on the
label
;

connect the load cables to load terminal block XR2 carefully respecting the

earth, neutral and phase correspondence as indicated on the label;

connect the various options as indicated in the corresponding sections of this

manual;

once the cables have been connected, each cable’s sleeving must be secured

against the horizontal hooping bar located above the terminal block by a hoop in
order to protect the conductors from eventual tensile stress;

refit the connection cover panel.

Connections for Comet series 11 7.5/10kVA

Fig. 12

to load
(single-phase
+ earth)

from LV switchboard
(single-phase +
earth)

XR3
battery
(optional)

XR2
load

XR1
Mains 1

L1

L1

N

N

XR1
Mains 2
(optional)

L

+

L1

N

L