Start-up, Cont'), Inverter start-up – MGE UPS Systems Comet TM 5 - 30 kVA User Manual

Page 22

Advertising
background image

4.2

Comet installation and user manual: E-6761200XT/FA

Merlin Gerin by MGE UPS SYSTEMS

If the transfer conditions (AC input power within tolerances) are correct, the
inverter comes on line and supplies the load,

■

■

the green "load protected" light 21 remains on,

In the event of a fault, the red "load not protected" light goes on. See the "alarms
section".

start-up

(cont')

21

I

+ –

!

!

O

22

18

inverter start-up

(system in manual start-up mode)

■

press the green "inverter on" button 22 :

■

■

the green "load protected" light 21 flashes,

■

■

the inverter 7 starts and if the transfer conditions are correct, the load is

transferred to the inverter,

■

■

the red "load not protected" light 18 goes off,

■

■

the green "load protected" light 21 goes on.

21

I

+ –

!

!

O

22

18