Comet series 31 general characteristics – MGE UPS Systems Comet TM 5 - 30 kVA User Manual

Page 51

Advertising
background image

Comet installation and user manual: E-6761200XT/FB

11.3

Merlin Gerin by MGE UPS SYSTEMS

Comet series 31 general characteristics

■

apparent power (kVA):

5

7.5

10

15

20

■

active power (kW):

4

6

8

12

16

■

efficiency (%):

91

91

91

92

92

■

heat losses (W):

445

668

890

1335 1780

■

noise level (dBa):

■

■

on RL load:

45

46

46

50

50

■

■

on RCD load:

50

53

53

53

53

■

battery backup time (minutes):

■

■

at rated load (power factor 0.6):

8

10

10

10

10

■

maximum leakage current (mA):

■

■

directly earthed neutral system (TT):

5

11

11

24

24

■

■

during a fault with an impedent neutral system: 23

45

45

102

102

■

dimensions and weight

■

■

height (mm):

730

910

910

1085 1085

■

■

width (mm):

360

400

400

560

560

■

■

depth (mm):

420

550

550

680

680

■

■

weight (kg):

90

190

210

390

450

■

AC input

■

■

number of phases:

3

■

■

voltage (V):

323 to 444

■

■

frequency (Hz):

47 to 63

■

■

power factor:

> 0.95

■

■

current distortion (%):

< 26

■

■

inrush current:

< In

■

AC output

■

■

number of phases:

1

■

■

voltage (V):

220 / 230 / 240

■

■

voltage tolerance (%):

±

1

■

■

frequency (Hz):

50 / 60

■

■

frequency tolerance (free-running) (%):

±

0.1

■

■

frequency tolerance (synchronized) (%):

±

1 /

±

1.5 /

±

2 /

±

3 /

±

4

■

■

synchronization rate (Hz/s):

1 / 2