NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE.

Figure 15

Figure 16

AIR INLET BAFFLE

GRATE

VENT RESTRICTOR INSTALLATION

RESTRICTOR

APPLIANCE VENT OUTLET

Install.the.restrictor.as.shown.from

inside.the.unit,.in.the.inner.fireplace.collar.

When.vertically.terminating.the.vent.system.above

the.roof,.install.a.vent.restrictor.in.the.top.vent.of

the.fireplace.outlet.

Step 3. INSTALL THE VENT SYSTEM

.

General Information

These instructions should be used as a guide-

line and do not supersede local codes in any

way. Install vent according to local codes,

these instructions, the current National Fuel

Gas Code (ANSI-Z223.1) in the USA or the

current standards of CAN/CGA-B149.1 and

-B149.2 in Canada.

Ensure clearances are in accordance with

local installation codes and the requirements

of the gas supplier.

Dégagement.conforme.aux.codes.d'installation.

locaux. et. aux. exigences. du. foumisseunde.

gaz.

Use only approved venting components.

See Approved Vent Components on

Page 2.

These fireplaces must be vented directly

to the outside.

The. vent. system. may. not. service. multiple.

appliances,.and.must.never.be.connected.to.a.

flue.serving.a.solid.fuel.burning.appliance..The..

vent.pipe.is.tested.to.be.run.inside.an.enclosing.

wall.(such.as.a.chase)..There.is.no.requirement.

for.inspection.openings.in.the.enclosing.wall.at.

any.of.the.joints.in.the.vent.pipe..

Installation of Vent Restrictor

A.vent.restrictor.may.be.needed.with.this.appli-

ance...The.restrictor.is.installed.in.the.appliance.

top.flue.outlet.as.shown.in.

Figure 15,

For vertical venting from 6 feet to 12 feet or

more, from the top of the fireplace to the top

of the termination, the installation of a vent

restrictor is required.

If.necessary,.install.a.vent.restrictor.in.the.ap-

pliance.flue.outlet.as.shown.in.

Figure 15..It.is.

held.in.place.by.friction,.only.

Note: The restrictor is included within the

firebox.

Select Venting System - Horizontal or Verti-

cal

With. the. appliance. secured. in. framing,. de-

termine.vent.routing.and.identify.the.exterior.

termination.location..The.following.sections.

describe.vertical.(roof).and.horizontal.(exterior.

wall).vent.applications..Refer.to.the.section.

relating.to.your.installation. A list of approved

venting components is shown on Page 30.