Dca-15spxu4 — maintenance – Multiquip Whisperwatt 60 Hz Generator DCA-15SPXU4 User Manual

Page 36

Advertising
background image

PAGE 36 — DCA-15SPXU4— OPERATION MANUAL — REV. #0 (03/31/11)

DCA-15SPXU4 — MAINTENANCE

To ensure adequate starting
capability, always have power
applied to the generator's
internal battery charger.

NOTE

Figure 36. Battery Charger &

Jacket Water Heater Power Connections

Jacket Water Heater and Internal Battery Charger
120 VAC Input Receptacles (OPTIONAL)

This generator can be optionally equipped with two 120 VAC,
20 amp input receptacles located on the output terminal
panel.

The purpose of these receptacles is to provide power via
commercial power to the

jacket water heater and internal

battery charger.

These receptacles will ONLY function when commercial
power has been supplied to them (Figure 36). To apply
commercial power to these receptacles, a power cord of
adequate size will be required (See Table 6).

When using the generator in

hot climates there is no reason

to apply power to jacket water heater. However, if the
generator will be used in

cold climates it is always a good

idea to apply power to the jacket water heater at all times. To
apply power to the jacket water heater simply apply power to
the jacket water heater receptacle via commercial power
using an power cord of adequate size.

If the generator will be used daily, the battery should normally
not require charging. If the generator will be idle (not used)
for long periods of time, apply power to the battery charger
receptacle via commercial power using an power cord of
adequate size.

Advertising
This manual is related to the following products: