Troubleshooting – Cornelius CH Series User Manual

Page 9

Advertising
background image

7

92266

TROUBLESHOOTING

WARNING: Disconnect electrical power to the Chiller to prevent personal injury before

attempting any internal maintenance. Only qualified personnel should service internal

components or electrical wiring.

TROUBLE

PROBABLE CAUSE

REMEDY

CHILLER DOES NOT

OPERATE, CONTROL

POWER LIGHT “OFF”

A. No Power To Unit.

A. Check Main disconnect fuses,

wiring, and power lead to unit.

B. Defective Control Power

Switch.

B. Replace Switch

C. Defective Control Transformer. C. Replace Transformer
D. Wrong Voltage Supplied to

Unit.

D. Supplied Voltage Must be within

± 10% of nameplate rating.

E. 3--Phase Monitor tripped.

E. Check for correct voltage level on

each phase of incoming 3--phase

power. Check for correct phase

rotation.

PUMP DOES NOT OPERATE,

BUT COOLING LIGHT IS

”ON”.

A. Line to or from Chiller is

restricted.

A. Inspect lines and remove any

obstructions.

B. Internal or external filter is

blocked with debris.

B. Remove filter, back-flush, and

replace.

C. Pump Contactor is

defective.

C. Replace.

D. Damaged pump motor or

impeller.

D. Replace pump motor or impeller.

CHILLER DOES NOT COOL,

AND COOLING LIGHT IS

”OFF”.

A. Thermostat is defective.

A. Replace Thermostat

PUMP RUNS, COMPRESSOR

”SHORT CYCLES”.

A. No process load on

chiller.

A. Increase process load.

B. Refrigerant is low.

B. Check refrigerant charge.

UNIT RUNS CONTINUOUSLY,

BUT IS NOT COOLING

PROCESS LIQUID ENOUGH.

A. Condenser is restricted.

A. Clean condenser.

B. Unit low on refrigerant.

B. Call Service.

C. Inefficient compressor.

C. Call Service.

D. Unit is undersized for

application.

D. Call REMCOR Chiller Sales Rep.