1 modbus plus message routing paths, 1 routing to programmable controllers – Schneider Electric Modicon BM85 User Manual

Page 28

Advertising
background image

Device Addressing and Message Routing

890 USE 103 00

18

2.1 Modbus Plus Message Routing Paths

A single Modbus Plus network can have up to 64 addressable node

devices, with each device having a unique address of between 1 and 64.

Multiple networks can be joined through Bridge Plus devices. Devices

address each other across Bridge Plus devices by specifying routing

paths of five bytes, with each byte representing an address on the next

network. This routing method allows nodes in other networks to be

addressed up to four networks away from the originating node.

The routing path is imbedded in the Modbus Plus message frame as it is

sent from the originating node:

MESSAGE FRAME

ROUTING

PATH

ROUTING ADDRESS 1

ROUTING ADDRESS 2

ROUTING ADDRESS 3

ROUTING ADDRESS 4

ROUTING ADDRESS 5

MODBUS PLUS

EXAMPLE:

ROUTING ADDRESS 1 = 25

ROUTING ADDRESS 2 = 20

ROUTING ADDRESS 3 = 12

ROUTING ADDRESSES 4, 5 = 0
(NO FURTHER ROUTING)

START

END

Figure 4

Message Frame Routing Path Field

Figure 4 is an example of message routing to a programmable controller

through three networks that are joined by Bridge Plus node devices.

The message will first be routed to node 25, a Bridge Plus on the local

network. That node forwards the message on to a Bridge Plus at

address 20 on the second network. The second Bridge Plus forwards the

message to its final destination, node address 12 on the third network.

The zero contents of bytes 4 and 5 specify no further message routing.

2.1.1

Routing to Programmable Controllers

For programmable controllers, the last non-zero byte in the message

routing specifies the network node address of the controller (1 to 64).