Configuring the Programmable Models

890 USE 103 00

67

4.8 Indicator Codes During Downloading

During downloading or internal testing, the four serial ports are disabled

and their indicators are used to show system status and error codes.

Indicator layouts are shown in Figure 22.

4.8.1

Normal Download Codes

The normal codes appearing during downloading are:

Indication

Meaning

Port 4 –– Flashing two times per second

Ready for downloading

Port 3 –– ON intermittently

Receiving download from host

Port 2 –– ON (combined with port 3)

Writing to BM85 RAM

Port 1 –– ON (combined with port 3)

Erasing BM85 RAM

4.8.2

Error Codes

If an error occurs during downloading, or if the user calls the exit()

routine, the BM85 displays an error pattern in its four indicators.

The error pattern produces two 4-bit codes for two hexadecimal digits.

First, the indicators show a steady pattern for one second, indicating the

upper digit. Then they show a flashing pattern for one second with the

lower digit. The continuous and flashing patterns alternate repetitively.

Port 4 is the most significant bit in each code.

Indicators

Pattern

Hexadecimal Digit

4 – 3 – 2 – 1

Steady

Upper digit

4 – 3 – 2 – 1

Flashing

Lower digit

Error Code
(Hexadecimal)

Meaning

F1

BM85 kernel is reloading

F4

Program or task returned to BM85 bootstrap

F8

Program or task called abort()

FD

Could not extend heap – program called malloc() or equivalent
and had insufficient memory

FE

Could not create heap – not enough memory below code area

FF

Not enough memory to copy program to RAM area