Configuring the Modbus Models

890 USE 103 00

40

3.5 Configuring the Modbus Ports

3.5.1

Connecting Power for the Configuration

Refer to the Installation chapter in this guide for connecting power to

your BM85. Connect the source of AC or DC power to the BM85. Do

not turn on the power to the BM85 until you set the Modbus port

configuration switches and connect the configuration terminal. The

switch settings will be sensed when power is applied.

3.5.2

Setting the Switches

The BM85 power should be off at this time. Switches are located on the

BM85 rear panel. Figure 10 shows the switch positions and setup.

1 2 3 4 5 6 7 8

SWITCH POSITION

1 2 3 4 5 6 7 8

PORT MODE:

CONFIGURE

RUN

CONFIGURATION PORT:

PORT 1
PORT 2
PORT 3
PORT 4

PARITY:

DISABLED

EVEN

DISABLED

ODD

BAUD RATE:

9600
2400
1200
300

UP

UP
UP

DOWN

DOWN
DOWN

UP

UP

DOWN

DOWN

UP = 1 DOWN = 2

NW–BM85–000

NW–BM85C002
NW–BM85D008

USE

UPPER

SWITCHES

USE

RIGHT

SWITCHES

NW–BM85–000 = STOP BITS:

UP = RUN APPLICATION

NW–BM85C002
NW–BM85D008 = MODE:

(LEAVE IN UP POSITION)

UP
UP
DOWN
DOWN

UP

UP

DOWN

DOWN

UP
UP
DOWN
DOWN

UP

UP

DOWN

DOWN

Figure 10

BM85 Modbus Models: Port Configuration Switches