11. PROCESSES AND FUNCTIONS

(2)

Freeze Prevention

Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the
efficiency of the unit, and frost buildup on the coil blocks cool air circulation from the indoor
unit’s fan.

Fig. 9

COMPRESSOR

OUTDOOR FAN

INDOOR FAN

OFF

OFF

OFF

OFF

INDOOR COIL
TEMPERATURE

MORE THAN 10 MINUTES

FREEZE
PREVENTION

6 MINUTES

10 MINUTES

FREEZE
PREVENTION

6 MINUTES

(THERMO ON)

30

°

F

ON

ON

ON

ON

ON

ON

1029_X_S

SET SPEED

(THERMO OFF)

(3)

Drain Pump Control

Drain pump operates when compressor starts to operate or when Float Switch turns off.

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

SET SPEED

OFF

OFF

OFF

OFF

OFF

OFF

FLOAT SWITCH

ON: low water level
OFF: high water level

COMPRESSOR

DRAIN PUMP

OUTDOOR FAN

INDOOR FAN

20 MINUTES

0609_X_S

Fig. 10