Introduction – Siemens DTU3005-B User Manual

Page 7

Advertising
background image

1

Introduction

Siemens Energy & Automation, Inc.

3

1.4.2

Modbus Master to SEAbus

The DTU3005 unit can be configured as a Modbus
(RTU) slave. In this configuration, a Modbus master
device (usually a SCADA system) is connected to port
1. The Modbus master uses the DTU3005 to monitor
and/or control Siemens ACCESS devices. A typical
Modbus application is shown below in Figure 1.5. The
passthrough port (port 3) can be used to connect to a
supervisory computer running WinPM software. It can
also be used to connect to a second, independent
Modbus Master device. This is shown in Figure 1.6.
Up to 32 DTU3005B units can be daisy chained using a
cable connected to port 1 of the three units. Each
DTU3005B device should have a different Modbus
device number. A daisy chained configuration is
shown in Figure 1.7.

Figure 1.5

Modbus Master to SEAbus

Figure 1.6

Two Independent Modbus Master Devices

to SEAbus

1 2 3

DTU3005B

Up to 32

ACCESS Devices

Acting as a Modbus

(RTU) slave. Data

is requested by

supervisory software.

Supervisory Software

on Modbus Master

RS-485

1 2 3

DTU3005B

Up to 32

ACCESS Devices

Acting as a Modbus

(RTU) slave. Data

is requested by

supervisory software.

Acting as a Modbus

(RTU) slave. Data

is requested by

supervisory software.

Supervisory Software

on Modbus Master

Independent Modbus Networks

Supervisory Software

on Modbus Master

RS-485

Advertising