Sanyo CL2472 User Manual

Page 97

Advertising
background image

8

(3) Installation procedure

Panel top

Panel front

Panel side R

Panel side L

Fig. 5j

1. Air Intake Baffle

(1) Left side

1. Remove the top panel from the unit.

2. Remove the panel side L, and drill 3 holes of ø1/4 inch

(6.5 mm) at the prescribed positions.

3. Install the windbaffle on the unit using field supply bolts

and nuts.

4. Recommended bolts to be used are 15/64" (M6 ISO

standard), and the recommended length of the bolts is

between 19/32 – 25/32 inch (15 – 20 mm).

5. Use washers and spring washers to tightly fasten the

windbaffle to the unit.

(2) Right side

1. Remove the top panel from the unit.

2. Use 2 preholes on the panel side R to install the baffle plate.

3. Remove the panel side R from the unit by removing the

screws. These screws are used in step 4 below.

4. Put (sandwich) the windbaffle between the unit and the

panel side R, then install the windbaffle on the unit using the

above screws. Be careful not to damage the screw holes.

2. Air Discharge Baffle

1. Remove the panels front, top, side L and R from the

unit and drill 4 holes of ø1/4 inch (6.5 mm) at the

prescribed positions.

2. Install the windbaffle on the unit using field supply

bolts and nuts.

3. Recommended bolts to be used are 15/64" (M6 ISO

standard), and the recommended length of the bolts

is between 13/32 – 19/32 inch (10 – 15 mm).

4. Use washers and spring washers to tightly fasten the

windbaffle to the unit.

(4) Precautions for installation

1. Be sure not to damage painted surfaces.

2. Finish the edges of the windbaffle to avoid cuts or injury.

3. Drilling of holes must be carefully done so that no damage is caused to external or internal parts of the unit.

Particular care must be taken that drill chips do not drop into the unit.

Fig. 5i

Panel side R

Panel top

Panel front

Panel side L

In order to prevent contact of the bolts and heat exchanger and other parts inside the unit, install the windbaffle using

bolts from inside the unit and fasten the bolts with nuts from outside the unit.

When the windbaffle is installed on the unit, the unit has higher wind resistance. In order to prevent the unit from

falling over, anchor the legs of the unit using anchor bolts (or similar method).

NOTE

07-154 CL1872-2472 6/12/07 3:19 PM Page 8