Schneider Electric 890USE17700 User Manual
Page 135
Advertising

Data Exchange
890USE17700 April 2004
135
List of Supported
Commands
The following table lists the Modbus commands that the STB NIP 2212 supports:
Modbus
Function
Code
Subfunction
or Subindex
Command
Valid Range Max. No. of
Words per
Message
3
read holding registers (4x)
1–9999
125
4
read input registers (3x)
1–4697
125
6
write single register (4x)
1–5120 and
9488–9999
1
8
21
get/clear Ethernet statistics (See
Ethernet Statistics, p. 136)
0–53
N/A
16
write multiple registers (4x)
1–5120 and
9488–9999
100
22
mask write registers (4x)
1–5120 and
9488–9999
1
23
read/write multiple registers (4x) 1–5120 and
9488–9999
100 (write)
1—9999
(read)
125 (read)
Advertising