A.1.5 functions – Siemens SIMATIC NET PROFIBUS User Manual
Page 244

Testing PROFIBUS
A-4
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
A.1.5
Functions
Checking the PROFIBUS Cable
In this test, the PROFIBUS cable alone is tested. The following errors can be
detected:
S
Short-circuit between data lines or between data line and shield
S
Line break
S
Shield break
S
Reversed polarity (A and B)
S
Reflections that could cause errors
S
Check of the number of activated terminating resistors
The length of the PROFIBUS cable can also be measured.
Checking the RS-485 Interface of a Slave
The test device is connected to one slave. This is supplied with power. The device
then makes the following measurements:
S
RS-485 driver OK/defective
S
Power supply to the terminating resistor OK/not OK
S
RTS signal present/not present
Checking the Accessibility of Nodes
S
List of accessible slaves (live list)
S
Addressing of specific slaves