Siemens SIMATIC NET PROFIBUS User Manual
Page 95
Advertising

Configuring Networks
3-29
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Table 3-9
Constants for Calculating the
Slot Time with DP Standard
(redundant optical ring)
Transmission
rate
a
b
c
12 Mbps
1651 240
28
6 Mbps
951 120
24
3 Mbps
551 60
24
1.5 Mbps
351 30
24
500 Kbps
251 10
24
187.5 Kbps
171 3.75
24
93.75 Kbps
171 1.875
24
45.45 Kbps
851 0.909
24
19.2 Kbps
171 0.384
24
9.6 Kbps
171 0.192
24
Table 3-10 Constants for Calculating the
Slot Time with DP/FMS (”Universal”) and DP
with S5–95U (redundant optical ring)
Transmission
rate
a
b
c
12 Mbps
1651 240
28
6 Mbps
951 120
24
3 Mbps
551 60
24
1.5 Mbps
2011 30
24
500 Kbps
771 10
24
187.5 Kbps
771 3.75
24
93.75 Kbps
451 1.875
24
45.45 Kbps
851 0.909
24
19.2 Kbps
181 0.384
24
9.6 Kbps
171 0.192
24
Advertising